Technical Data
257/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
10.4.24 CC Link Slave
Parameter
Description
Firmware works according to CC-Link Version 2.0:
Station Types
Remote Device Station (up to 4 occupied stations)
Maximum input data
368 bytes
Maximum output data
368 bytes
Input data remote device station
112 bytes (RY) and 256 bytes (RWw)
Output data remote device station
112 bytes (RX) and 256 bytes (RWr)
Extension cycles
1, 2, 4, 8
Baud rates
156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
Limitation
Intelligent Device Station not supported
Firmware works according to CC-Link Version 1.11:
Station Types
Remote I/O station,
Remote device station’ (up to 4 occupied stations)
Maximum input data
48 bytes
Maximum output data
48 bytes
Input data remote I/O station
4 bytes (RY)
Output data remote I/O station
4 bytes (RX)
Input data remote device station
4 bytes (RY) and 8 bytes (RWw) per occupied station
Output data remote device station
4 bytes (RX) and 8 bytes (RWr) per occupied station
Baud rates
156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
Firmware
Reference to firmware/stack version
V2.12
Table 192: Technical Data CC-Link-Slave-Protocol