![background image](http://html1.mh-extra.com/html/ge/ur-series/ur-series_manual_4212129302.webp)
3-86
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.8 Transformer aging factor (Age)
This element is instantiated in the following products: T60.
Table 3-85: Transformer aging data objects
3.5.3.9 Transformer hottest spot temperature (HPTmp)
This element is instantiated in the following products: T60.
Table 3-86: Hottest spot temperature data objects
setSrcRef
ObjectReference
SP AR# ADD DELAY 2 setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
AgeSPTR1
LDevice inst:
Ctrl
UR element:
Aging Factor Function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
XFMR AGING FCTR OP
R
general
BOOLEAN
ST XFMR AGING FCTR OP
R
Dpo
SPS
XFMR AGING FCTR DPO operand
R
stVal
BOOLEAN
ST XFMR AGING FCTR DPO
R
Str
ACD
XFMR AGING FCTR PKP operand
R
general
BOOLEAN
ST XFMR AGING FCTR PKP
R
dirGeneral
ENUMERATED
ST
0
R
AgeRte
MV
AGING FACTOR actual Values
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
AGING FACTOR
R
mag
Analogue Value
MX
R
mag.f
FLOAT32
instMag.i on deadband exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0 is multiplier for 1
R
db
INT32U
CF AgeSPTR1.AgeRte.db
R/W/C
zeroDb
INT32U
CF
0
R
BlkRef
γ
ORG
AGING FACTOR BLOCK for setting group
γ
R
setSrcRef
ObjectReference
SP AGING FACTOR BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
HPTmpSPTR1
LDevice inst:
Ctrl
UR element:
Hottest-Spot Temperature Function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
XFMR HST-SPOT
˚
C OP
R
general
BOOLEAN
ST XFMR HST-SPOT
˚
C OP
R
Dpo
SPS
XFMR HST-SPOT °C DPO operand
R
stVal
BOOLEAN
ST XFMR HST-SPOT °C DPO
R
Str
ACD
XFMR HST-SPOT °C PKP operand
R
general
BOOLEAN
ST XFMR HST-SPOT °C PKP
R
dirGeneral
ENUMERATED
ST
0
R
ToOilTmp
MV
TOP OIL °C actual Value
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
TOP OIL °C
R
mag
Analogue Value
MX
R
mag.f
FLOAT32
instMag.i on deadband exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
23, the code for °C
R
LNName:
Rec3pRREC#
LDevice inst:
Ctrl
UR element:
Autoreclose element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...