2-58
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
46BB
Incipient Cable Fault Detector 1 Reset
Delay
0 to 65.535
s
0.001 F001
100
"
46BC
Incipient Cable Fault Detector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
46BD
Incipient Cable Fault Detector 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
46BE
...Repeated for Incipient Cable Fault
Detector 2
F35
46CA
...Repeated for Incipient Cable Fault
Detector 3
"
46D6
...Repeated for Incipient Cable Fault
Detector 4
"
46E2
...Repeated for Incipient Cable Fault
Detector 5
"
46EE
...Repeated for Incipient Cable Fault
Detector 6
Breaker Control (Read/Write Settings) (2, 4, or 6 Modules)
All except B90
47D0
Breaker 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
47D1
Breaker 1 Name
---
---
---
F206
“Bkr 1"
"
47D4
Breaker 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
"
47D5
Breaker 1 Open
0 to 4294967295
---
1
F300
0
"
47D7
Breaker 1 Close
0 to 4294967295
---
1
F300
0
"
47D9
Breaker 1 Phase A / Three-pole Closed
0 to 4294967295
---
1
F300
0
"
47DB
Breaker 1 Phase B Closed
0 to 4294967295
---
1
F300
0
"
47DD
Breaker 1 Phase C Closed
0 to 4294967295
---
1
F300
0
"
47DF
Breaker 1 External Alarm
0 to 4294967295
---
1
F300
0
"
47E1
Breaker 1 Alarm Delay
0 to 65.535
s
0.001 F003
0
"
47E3
Breaker 1 Pushbutton Control
0 to 1
---
1
F102
0 (Disabled)
"
47E4
Breaker 1 Manual Close Recall Time
0 to 65.535
s
0.001 F003
0
"
47E6
Breaker 1 Out of Service
0 to 4294967295
---
1
F300
0
"
47E8
Breaker 1 Block Open
0 to 4294967295
---
1
F300
0
"
47EA
Breaker 1 Block Close
0 to 4294967295
---
1
F300
0
"
47EC
Breaker 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
"
47EE
Breaker 1 Phase B Opened
0 to 4294967295
---
1
F300
0
"
47F0
Breaker 1 Phase C Opened
0 to 4294967295
---
1
F300
0
"
47F2
Breaker 1 Operate Time
0 to 65535
ms
1
F003
70
"
47F4
Breaker 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
47F5
Reserved
0 to 65535
s
1
F001
0
"
47F6
...Repeated for Breaker 2
B30, C60, C70,
D60, F60, F35,
G30, G60, L60,
L90, M60, N60,
T35, T60
481C
...Repeated for Breaker 3
"
4842
...Repeated for Breaker 4
B30, C70, F35,
N60, T35, T60
4868
...Repeated for Breaker 5
"
488E
...Repeated for Breaker 6
Compensated Overvoltage (Read/Write Grouped Setting)
D60
48F0
Compensated OV Function
0 to 1
---
1
F102
0 (Disabled)
"
48F1
Compensated OV Source
0 to 5
---
1
F167
0 (SRC 1)
"
48F2
Compensated OV Zc Mag
0 to 500
ohm
0.01
F001
200
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...