![background image](http://html1.mh-extra.com/html/ge/ur-series/ur-series_manual_4212129282.webp)
3-66
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.38 Phase instantaneous overcurrent (PhsIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-59: Phase instantaneous overcurrent data objects
3.5.2.39 Phase overvoltage (PhsOv)
This element is instantiated in the following products: C60, C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-60: Phase overvoltage data objects
LNName:
PhsIocPIOC#
LDevice inst:
Prot
UR element:
Phase Instantaneous Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE IOC# PKP operands (including
individual three phases), which indicates
that Op operates when delay expires
R
general
BOOLEAN
ST PHASE IOC# PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
phsA
BOOLEAN
ST PHASE IOC# PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown
R
phsB
BOOLEAN
ST PHASE IOC# PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown
R
phsC
BOOLEAN
ST PHASE IOC# PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
PHASE IOC# OP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE IOC# OP
R
phsA
BOOLEAN
ST PHASE IOC# OP A
R
phsB
BOOLEAN
ST PHASE IOC# OP B
R
phsC
BOOLEAN
ST PHASE IOC# OP C
R
Dpo
SPS
PHASE IOC# DPO operand
R
stVal
BOOLEAN
ST PHASE IOC# DPO
R
DpoPhs
β
SPS
PHASE IOC# DPO
β
operands” (where
β
refers to Phase-A, B or C)
R
stVal
BOOLEAN
ST PHASE IOC# DPO
β
(where
β
refers
to Phase-A, B or C)
R
BlkRef
γβ
ORG
PHASE IOC# BLOCK
β
setting for setting
group
γ
.” (where
β
refers to Phase-A, B or C)
R
setSrcRef
ObjectReference
SP PHASE IOC# BLOCK
β
(where
β
refers to Phase-A, B or C)
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PhsOvPTOV#
LDevice inst:
Prot
UR element:
Phase Overvoltage element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHASE OV # PKP operands (including
individual three phases)
R
general
BOOLEAN
ST PHASE OV # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsA
BOOLEAN
ST PHASE OV # PKP A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsB
BOOLEAN
ST PHASE OV # PKP B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
phsC
BOOLEAN
ST PHASE OV # PKP C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...