CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-65
3
Table 3-57: Phase directional data objects
3.5.2.37 Phase distance (PhsDis)
This element is instantiated in the following products: D30, D60, G60, L60, L90, T60.
Table 3-58: Phase distance data objects
LNName:
PhsDirRDIR#
LDevice inst:
Prot
UR element:
Phase Directional element # (ANSI 67P)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Dir
ACD
PH DIR # BLK operand, which becomes On
when phase current is flowing in the set
direction
R
general
BOOLEAN
ST PH DIR # BLK
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element can be connected/configured
to look forward or backward.
R
phsA
BOOLEAN
ST PH DIR # BLK A
R
dirPhsA
ENUMERATED
ST
0, the code for unknown
R
phsB
BOOLEAN
ST PH DIR # BLK B
R
dirPhsB
ENUMERATED
ST
0, the code for unknown
R
phsC
BOOLEAN
ST PH DIR # BLK C
R
dirPhsC
ENUMERATED
ST
0, the code for unknown
R
BlkRef
γ
ORG
PHASE DIR # BLOCK setting for setting
group
γ
R
setSrcRef
ObjectReference
SP PHASE DIR # BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PhsDisPDIS#
LDevice inst:
Prot
UR element:
Phase Distance Z# settings
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
PHS DIST Z# PKP operand in Phase-To-
Phase
R
general
BOOLEAN
ST PH DIST Z# PKP
R
dirGeneral
ENUMERATED
ST
1(Forward) if PHS DIST Z DIR value is
Forward, 2 (backward) if PHS DIST Z1 DIR
value is Reverse, and otherwise 0 (unknown)
R
Op
ACT
PHS DIST Z# OP operand in Phase-To-Phase
R
general
BOOLEAN
ST PHS DIST Z# OP
R
StrPhs
φ
SPS
PHS DIST Z# PKP
θ
operand in Phase-To-
Phase
R
stVal
BOOLEAN
ST PHS DIST Z# PKP
θ
R
DpoPhs
φ
SPS
PHS DIST Z# DPO
θ
operand in Phase-To-
Phase
R
stVal
BOOLEAN
ST PHS DIST Z# DPO
θ
R
OpPhs
φ
SPS
PH DIST Z # OP
θ
operand
R
stVal
BOOLEAN
ST PH DIST Z# OP
θ
R
ASupn
φ
SPS
PHS DIST Z# SUPN
θ
operand in Phase-To-
Phase
R
stVal
BOOLEAN
ST PHS DIST Z# SUPN
θ
R
BlkRef
γ
ORG
PHS DIST Z# BLK setting for setting group
γ
R
setSrcRef
ObjectReference
SP PHS DIST Z# BLK.
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
2
ORG
Instantiated only in logical node instance 1
R
setSrcRef
ObjectReference
SP Setting FORCE SELF-POLAR
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
3
ORG
Instantiated only in logical node instance 1
R
setSrcRef
ObjectReference
SP Setting FORCE MEM-POLAR l
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...