MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
6642
Field Ground Current
0 to 655.35
mA
0.01
F001
0
"
6643
Field Ground Injected Voltage
-32.767 to 32.767
V
0.001 F002
0
"
6644
Field Ground Fault Location
-30000 to 30000
%
1
F002
-10
"
6645
Field Ground Field Voltage
-3276.8 to 3276.7
V
0.1
F002
0
"
6646
Field Current
-9999.999 to
9999.999
---
0.001 F004
0
"
6648
Field Current Units
---
---
---
F206
"A"
Accidental Energization (Read/Write Grouped Setting)
G30, G60
6650
Accidental Energization Function
0 to 1
---
1
F102
0 (Disabled)
"
6651
Accidental Energization Source
0 to 5
---
1
F167
0 (SRC 1)
"
6652
Accidental Energization Arming Mode
0 to 1
---
1
F193
0 (UV AND
OFFLINE)
"
6653
Accidental Energization OC Pickup
0 to 3
pu
0.001 F003
300
"
6655
Accidental Energization UV Pickup
0 to 3
pu
0.001 F003
500
"
6657
Accidental Energization Offline
0 to 4294967295
---
1
F300
0
"
6659
Accidental Energization Block
0 to 4294967295
---
1
F300
0
"
665B
Accidental Energization Target
0 to 2
---
1
F109
0 (Self-reset)
"
665C
Accidental Energization Events
0 to 1
---
1
F102
0 (Disabled)
"
665D
Reserved (5 items)
0 to 65535
---
1
F001
0
Loss of Excitation (Read/Write Grouped Setting)
G30, G60
666A
Loss Of Excitation Function
0 to 1
---
1
F102
0 (Disabled)
"
666B
Loss Of Excitation Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
666C
Loss Of Excitation Center 1
0.1 to 300
ohm
0.01
F001
1000
"
666D
Loss Of Excitation Radius 1
0.1 to 300
ohm
0.01
F001
800
"
666E
Loss Of Excitation UV Supervision Enable 1 0 to 1
---
1
F102
1 (Enabled)
"
666F
Loss Of Excitation Pickup Delay 1
0 to 65.535
s
0.001 F001
50
"
6670
Loss Of Excitation Center 2
0.1 to 300
ohm
0.01
F001
1200
"
6671
Loss Of Excitation Radius 2
0.1 to 300
ohm
0.01
F001
1000
"
6672
Loss Of Excitation UV Supervision Enable 2 0 to 1
---
1
F102
1 (Enabled)
"
6673
Loss Of Excitation Pickup Delay 2
0 to 65.535
s
0.001 F001
500
"
6674
Loss Of Excitation UV Supervision
0 to 1.25
pu
0.001 F001
700
"
6675
Loss Of Excitation Block
0 to 4294967295
---
1
F300
0
"
6677
Loss Of Excitation Target
0 to 2
---
1
F109
0 (Self-reset)
"
6678
Loss Of Excitation Events
0 to 1
---
1
F102
0 (Disabled)
"
6679
Reserved (5 items)
0 to 65535
---
1
F001
0
Bus Configuration (Read/Write Setting) (6 Modules)
B90
667E
...Repeated for Bus Zone 3
Sensitive Directional Power (Read/Write Grouped Setting) (2 Modules)
C60, D60, F60,
G30, G60, L90,
M60, N60
6680
Sensitive Directional Power 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
6681
Sensitive Directional Power 1 Signal Source 0 to 5
---
1
F167
0 (SRC 1)
"
6682
Sensitive Directional Power 1 RCA
0 to 359
degrees 1
F001
0
"
6683
Sensitive Directional Power 1 Calibration
0 to 0.95
degrees 0.05
F001
0
"
6684
Sensitive Directional Power 1 STG1 SMIN
-1.2 to 1.2
pu
0.001 F002
100
"
6685
Sensitive Directional Power 1 STG1 Delay
0 to 600
s
0.01
F001
50
"
6686
Sensitive Directional Power 1 STG2 SMIN
-1.2 to 1.2
pu
0.001 F002
100
"
6687
Sensitive Directional Power 1 STG2 Delay
0 to 600
s
0.01
F001
2000
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...