CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-77
2
"
6452
...Repeated for Negative Sequence
Overvoltage 3
Overfrequency (Read/Write Setting) (4 Modules)
D60, F60, G30,
G60, L90, M60,
N60, T60
6470
Overfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
6471
Overfrequency 1 Block
0 to 4294967295
---
1
F300
0
"
6473
Overfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
6474
Overfrequency 1 Pickup
20 to 65
Hz
0.01
F001
6050
"
6475
Overfrequency 1 Pickup Delay
0 to 65.535
s
0.001 F001
500
"
6476
Overfrequency 1 Reset Delay
0 to 65.535
s
0.001 F001
500
"
6477
Overfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
6478
Overfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
6479
Reserved (4 items)
0 to 1
---
1
F001
0
"
647D
...Repeated for Overfrequency 2
"
648A
...Repeated for Overfrequency 3
"
6497
...Repeated for Overfrequency 4
Bus Configuration (Read/Write Setting) (2 Modules)
B30
64B0
Bus Zone xA Source (6 items)
0 to 5
---
1
F167
0 (SRC 1)
"
64B6
Bus Zone xA Status (6 items)
0 to 4294967295
---
1
F300
0
"
64C2
...Repeated for Bus Zone 2
Bus Differential (Read/Write Grouped Setting) (4 or 6 Modules)
B30, B90
64E0
Bus Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
64E1
Bus Zone 1 Pickup
0.05 to 6
pu
0.001 F001
100
"
64E2
Bus Zone 1 Low Slope
15 to 100
%
1
F001
25
"
64E3
Bus Zone 1 Low Breakpoint
1 to 30
pu
0.01
F001
200
"
64E4
Bus Zone 1 High Slope
50 to 100
%
1
F001
60
"
64E5
Bus Zone 1 High Breakpoint
1 to 30
pu
0.01
F001
800
"
64E6
Bus Zone 1 High Set
0.1 to 99.99
pu
0.01
F001
1500
"
64E7
Bus Zone 1 Seal In
0 to 65.535
s
0.001 F001
400
"
64E8
Bus Zone 1 Block
0 to 4294967295
---
1
F300
0
"
64EA
Bus Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
64EB
Bus Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
B90
64EC
Bus Zone 1 Supervision
0 to 4294967295
---
1
F300
1
B90
64F6
Bus Zone 1 Trip
0 to 4294967295
---
1
F300
0
B30, B90
64F8
...Repeated for Bus Zone 2
"
6510
...Repeated for Bus Zone 3
"
6528
...Repeated for Bus Zone 4
B90
6540
...Repeated for Bus Zone 5
"
6558
...Repeated for Bus Zone 6
Time of Day Timer (Read/Write Setting) (5 Modules)
C70
6570
Time of Day Timer 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
6571
Time of Day Timer 1 Start Time
0 to 2359
---
1
F050
0
"
6573
Time of Day Timer 1 Stop Time
0 to 2359
---
1
F050
2359
"
6575
Time of Day Timer 1 Targets
0 to 2
---
1
F109
0 (Self-reset)
"
6576
Time of Day Timer 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
6577
...Repeated for Time of Day Timer 2
"
657E
...Repeated for Time of Day Timer 3
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...