3-124
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6.4 Digital elements (DigEl)
This element is instantiated in the following products: B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90,
M60, N60, T35, T60.
Table 3-112: Digital element data objects
frEna
BOOLEAN
CF
R
strTm
TimeStamp
CF
0
R
frPd
INT32
CF
0
R
frRs
BOOLEAN
CF
R
InRef1
ORG
COUNTER # UP setting
R
setSrcRef
ObjectReference
SP COUNTER # UP setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
COUNTER # DOWN setting
R
setSrcRef
ObjectReference
SP COUNTER # DOWN setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef3
ORG
CNT# SET TO PRESET setting
R
setSrcRef
ObjectReference
SP CNT# SET TO PRESET setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef4
ORG
COUNTER # RESET setting
R
setSrcRef
ObjectReference
SP COUNTER # RESET setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef5
ORG
COUNTER # FREEZE/RESET setting
R
setSrcRef
ObjectReference
SP COUNTER # FREEZE/RESET setting Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef6
ORG
COUNTER # FREEZE/COUNT setting
R
setSrcRef
ObjectReference
SP COUNTER # FREEZE/COUNT
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
COUNTER # BLOCK setting
R
setSrcRef
ObjectReference
SP COUNTER # BLOCK setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
DigElGAPC#
LDevice inst:
Gen
UR element:
Digital Element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
Dig Element # PKP operand, which indicates
that Op operates when delay expires
R
general
BOOLEAN
ST Dig Element #(DE#) PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
Dig Element # OP operand, which becomes
On when the input is On, and the element is
not blocked
R
general
BOOLEAN
ST Dig Element #(DE#) OP
R
Dpo
SPS
Dig Element # DPO operand, which
indicates that the element drops out (Reset)
when delay expires
R
stVal
BOOLEAN
ST Dig Element #(DE#) DPO
R
InRef1
ORG
DIG ELEM #INPUT setting
R
setSrcRef
ObjectReference
SP DIG ELEM #INPUT setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
DIG ELEM # BLOCK setting
R
setSrcRef
ObjectReference
SP DIG ELEM # BLOCK
Reference to the data attribute to input
R/C
LNName:
DigCntFCNT#
LDevice inst:
Gen
UR element:
Digital Counters #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...