CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-93
3
3.5.4.5 Contact input interface (ConIn)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-94: Contact input data objects
3.5.4.6 Contact output interface (ConOut)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-95: Contact output data objects
setSrcRef
ObjectReference
SP BREAKER #
φ
A/3P CLSD if
Θ
=”1”,
BREAKER #
φ
B CLSD if
Θ
=”2”, or
BREAKER #
φ
C CLSD if
Θ
=”3”
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
BREAKER #
φ
A/3P OPND setting” if
Θ
=”1”,
“BREAKER #
φ
B OPND setting” if
Θ
=”2”, or
“BREAKER #
φ
C OPND setting” if
Θ
=”3
R
setSrcRef
ObjectReference
SP BREAKER #
φ
A/3P OPND if
Θ
=”1”,
BREAKER #
φ
B OPND if
Θ
=”2”, or
BREAKER #
φ
C OPND if
Θ
=”3”
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
ConInGGIO1
LDevice inst:
System
UR element:
Contact Inputs
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind1
Θ
SPS
Concatenation of value of CONTACT INPUT
φ
ID + “ On (
φ
) operand value
R
stVal
BOOLEAN
ST Cont Ip
φ
On
R
Ind2
Θ
SPS
Concatenation of value of CONTACT INPUT
φ
ID + “ Off (
φ
) operand value
R
stVal
BOOLEAN
ST Cont Ip
φ
Off
R
LNName:
ConOutGGIO1
LDevice inst:
System
UR element:
Contact Outputs
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Ind1
Θ
SPS
Only instantiated where the order code
indicates that contact output
Θ
is equipped
with a current detector
R
stVal
BOOLEAN
ST Cont Op
φ
IOn
R
Ind2
Θ
SPS
Only instantiated where the order code
indicates that contact output
Θ
is equipped
with a voltage detector
R
stVal
BOOLEAN
ST Cont Op
φ
VOn
R
Ind3
Θ
SPS
Only instantiated where the order code
indicates that contact output
Θ
is equipped
with a voltage detector
R
stVal
BOOLEAN
ST Cont Op
φ
VOff
R
InRef1
Θ
ORG
CONTACT OUTPUT
φ
OPERATE setting
R
setSrcRef
ObjectReference
SP CONTACT OUTPUT
φ
OPERATE
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
Θ
ORG
CONTACT OUTPUT
φ
SEAL-IN setting.
R
setSrcRef
ObjectReference
SP CONTACT OUTPUT
φ
SEAL-IN
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
Bkr
Θ
XCBR#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...