2-128
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
9E8A
...Repeated for Voltage Differential 3
Charge Current Compensation Settings (Read/Write Grouped Setting)
L60
9EF0
Charging Current Compensation Factor
0 to 1
---
1
F102
0 (Disabled)
"
9EF1
Charging Current Compensation Block
0 to 4294967295
---
1
F300
0
"
9EF3
Charging Current Compensation Positive-
Sequence Xc
0.100 to 65.535
kOhm
0.001 F001
100
"
9EF4
Charging Current Compensation Zero-
Sequence Xc
0.100 to 65.535
kOhm
0.001 F001
100
Undercurrent (Read/Write Grouped Setting)
M60
9F00
Undercurrent Function
0 to 1
---
1
F102
0 (Disabled)
"
9F01
Undercurrent Speed 1 Start Block Delay
0.00 to 600.00
s
0.01
F001
50
"
9F02
Undercurrent Speed 1 Alarm Pickup
0.10 to 0.95
× FLA
0.01
F001
70
"
9F03
Undercurrent Speed 1 Alarm Pickup Delay 0.00 to 600.00
s
0.01
F001
200
"
9F04
Undercurrent Speed 1 Trip Pickup
0.10 to 0.95
× FLA
0.01
F001
70
"
9F05
Undercurrent Speed 1 Trip Pickup Delay
0.00 to 600.00
s
0.01
F001
100
"
9F06
Undercurrent Speed 1 Trip Reset Delay
0.00 to 600.00
s
0.01
F001
100
"
9F07
Undercurrent Speed 1 Block
0 to 4294967295
---
1
F300
0
"
9F09
Undercurrent Target
0 to 2
---
1
F109
0 (Self-reset)
"
9F0A
Undercurrent Events
0 to 1
---
1
F102
0 (Disabled)
"
9F0B
Undercurrent Speed 2 Start Block Delay
0.00 to 600.00
s
0.01
F001
50
"
9F0C
Undercurrent Speed 2 Alarm Pickup
0.10 to 0.95
× FLA
0.01
F001
70
"
9F0D
Undercurrent Speed 2 Alarm Pickup Delay 0.00 to 600.00
s
0.01
F001
200
"
9F0E
Undercurrent Speed 2 Trip Pickup
0.10 to 0.95
× FLA
0.01
F001
70
"
9F0F
Undercurrent Speed 2 Trip Pickup Delay
0.00 to 600.00
s
0.01
F001
100
"
9F10
Undercurrent Speed 2 Trip Reset Delay
0.00 to 600.00
s
0.01
F001
100
"
9F11
Undercurrent Speed 2 Block
0 to 4294967295
---
1
F300
0
"
9F13
Reserved (2 items)
0 to 1
---
1
F001
0
Cold Load Pickup (Read/Write Setting) (2 Modules)
F60
A000
Cold Load Pickup 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
A001
Cold Load Pickup 1 Initiate
0 to 4294967295
---
1
F300
0
"
A003
Cold Load Pickup 1 Block
0 to 4294967295
---
1
F300
0
"
A005
Outage Time Before Cold Load Pickup 1
0 to 1000
s
1
F001
1000
"
A006
On Load Time Before Reset 1
0 to 1000000
s
0.001 F003
100000
"
A008
Cold Load Pickup 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
A009
Cold Load Pickup 1 Reserved
0 to 65535
---
1
F001
0
"
A00A
...Repeated for Cold Load Pickup 2
Broken Rotor Bar Detection (Read Only Actual Values)
M60
A020
Broken Rotor Bar Component Level
–100 to 0
dB
0.1
F002
–1000
"
A021
Broken Rotor Bar Component Frequency
0 to 76
Hz
0.01
F001
0
"
A022
Motor Load at Broken Rotor Bar Calculation 0 to 1.5
× FLA
0.01
F001
0
"
A023
Motor Load Deviation at Broken Rotor Bar
Calculation
0 to 1.5
× FLA
0.01
F001
0
"
A024
Time Stamp at Broken Rotor Bar
Calculation
0 to 4294967295
---
1
F050
0
"
A026
Maximum Broken Rotor Bar Component
Level
–100 to 0
dB
0.1
F002
–1000
"
A027
Maximum Broken Rotor Bar Component
Frequency
0 to 76
Hz
0.01
F001
0
"
A028
Motor Load at Broken Rotor Bar Maximum 0 to 1.5
× FLA
0.01
F001
0
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...