CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-53
2
"
4194
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Clock (Read/Write Setting)
All
419F
Synchronizing Source
0 to 3
---
1
F623
0 (None)
Clock (Read/Write Command)
All
41A0
Real Time Clock Set Time
0 to 235959
---
1
F050
0
Clock (Read/Write Setting)
All
41A2
SR Date Format
0 to 4294967295
---
1
F051
0
"
41A4
SR Time Format
0 to 4294967295
---
1
F052
0
"
41A6
IRIG-B Signal Type
0 to 2
---
1
F114
0 (None)
"
41A7
Clock Events Enable / Disable
0 to 1
---
1
F102
0 (Disabled)
"
41A8
Time Zone Offset from UTC
–24 to 24
hours
0.5
F002
0
"
41A9
Daylight Savings Time (DST) Function
0 to 1
---
1
F102
0 (Disabled)
"
41AA
Daylight Savings Time (DST) Start Month
0 to 11
---
1
F237
0 (January)
"
41AB
Daylight Savings Time (DST) Start Day
0 to 6
---
1
F238
0 (Sunday)
"
41AC
Daylight Savings Time (DST) Start Day
Instance
0 to 4
---
1
F239
0 (First)
"
41AD
Daylight Savings Time (DST) Start Hour
0 to 23
---
1
F001
2
"
41AE
Daylight Savings Time (DST) Stop Month
0 to 11
---
1
F237
0 (January)
"
41AF
Daylight Savings Time (DST) Stop Day
0 to 6
---
1
F238
0 (Sunday)
"
41B0
Daylight Savings Time (DST) Stop Day
Instance
0 to 4
---
1
F239
0 (First)
"
41B1
Daylight Savings Time (DST) Stop Hour
0 to 23
---
1
F001
2
Fault Report Commands (Read/Write Command)
C60, D30, D60,
F35, F60, L30,
L60, L90
41B2
Fault Reports Clear Data Command
0 to 1
---
1
F126
0 (No)
Oscillography (Read/Write Setting)
C60, D30, D60,
F35, F60, G30,
G60, L90, M60,
T35, T60
41C0
Oscillography Number of Records
3 to 64
---
1
F001
5
B30, B90, C30,
C70, L30, L60,
N90
41C0
Oscillography Number of Records
3 to 64
---
1
F001
15
All
41C1
Oscillography Trigger Mode
0 to 1
---
1
F118
0 (Auto.
Overwrite)
"
41C2
Oscillography Trigger Position
0 to 100
%
1
F001
50
"
41C3
Oscillography Trigger Source
0 to 4294967295
---
1
F300
0
"
41C5
Oscillography AC Input Waveforms
0 to 4
---
1
F183
2 (16
samples/
cycle)
"
41D0
Oscillography Analog Channel x (16 items) 0 to 65535
---
1
F600
0
"
4200
Oscillography Digital Channel x (63 items)
0 to 4294967295
---
1
F300
0
Trip and Alarm LEDs (Read/Write Setting)
All
42B0
Trip LED Input FlexLogic Operand
0 to 4294967295
---
1
F300
0
"
42B2
Alarm LED Input FlexLogic Operand
0 to 4294967295
---
1
F300
0
User Programmable LEDs (Read/Write Setting) (48 Modules)
All
42C0
FlexLogic Operand to Activate LED
0 to 4294967295
---
1
F300
0
"
42C2
User LED type (latched or self-resetting)
0 to 1
---
1
F127
1 (Self-Reset)
"
42C3
...Repeated for User-Programmable LED 2
"
42C6
...Repeated for User-Programmable LED 3
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...