CHAPTER 3: IEC 61850 COMMUNICATION
SCL IMPLEMENTATION CONFORMANCE STATEMENT (SICS)
UR SERIES – COMMUNICATIONS GUIDE
3-135
3
3.6 SCL implementation conformance statement (SICS)
The table outlines conformance to the Substation Configuration Language (SCL).
Table 3-119: SCL conformance statement
Zero
MV
Analog 0 fixed operand
Master/LLN0
Zn1Extend
SPS
The zone 1 distance function must be set to the extended overreach value
Rec13pRREC
Zn2Tr
SPS
Operated from overreaching zone 2 when reclosing the line
LinPkpPIOC
UR
UR Setup
Value/comments
ICD Export
Yes
Yes
I11
Fix ICD file (no adaptable export needed)
Yes
Yes
I12
Export of ICD file or IID file according to IED
preconfiguration performed by tool
I13
State the data model name space (61850-7-3
subclause 7.2) within ICD file (LLN0.NamPlt.ldNs value)
Yes
Yes
I14
State the data model version (61850-7-3 subclause
7.8.3) and any predefined / fixed configuration values
within ICD file (9.5.4.4)
Yes
Yes
I15
Version 2003 export
I16
Version 2007 export
Yes
Yes
I17
Predefined data sets
I18
Predefined control blocks
Yes
Yes
I19
Substation bay template with IED part
I110
Communication section with default address
Yes
Yes
I111
Export correct valKind value (Table 46)
I112
Exports internal addresses as InRef or Input section
(subclause 9.3.13)
Yes
Yes
I113
Exports internal addresses in Input section with
expected serviceType (subclause 9.3.13)
I114
Exports in UTF-8 coding
Yes
Yes
SCD import
If renamed
CID
Yes
I21
Identify IED to be configured in SCD file by IED name
Yes
IP address
is used to
locate the
IED name
Yes
I22
Configure LD name (at least via ldInst, dependent on
the IED capabilities) and IED addresses from SCD
Yes
Yes
I23
Determine communication side addresses of IED inputs
from SCD
Yes
Yes
I24
Determine and use clock communication addresses
from SCD
I25
Configure values of (existing) control block from SCD
(9.3)
Yes
Yes
I26
Prepare (new) control block instances according to SCD
file
I26
Prepare / configure data sets according to SCD file
Yes
Yes
I28
Modify predefined data sets according to SCD
Data object
name
CDC
Semantics
Used in logical
nodes…
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...