CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-125
3
3.5.6.5 FlexElement element (FlxEl)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-113: FlexElement data objects
3.5.6.6 FlexLogic, FlexLogic timers, and virtual outputs (FlxLgc)
This element is instantiated all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60).
Table 3-114: FlexLogic data objects
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
FlxElGAPC#
LDevice inst:
Gen
UR element:
FlexElement element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
FxE # PKP operand, which becomes On
when this element has picked up
R
general
BOOLEAN
ST FxE # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
FxE # OP operand
R
general
BOOLEAN
ST FxE # OP
R
Dpo
SPS
FxE # DPO operand, which is the inverse of
FxE OP
R
stVal
BOOLEAN
ST FxE # DPO
R
OpSig
MV
FLEXELEMENT # OpSig, in per unit
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
FLEXELEMENT # OpSig
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
FLEXELEMENT # OpSig on
deadband exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless (per unit)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF FlxElGAPC#.OpSig.db
R/W/C
zeroDb
INT32U
CF
0
R
BlkRef1
ORG
FLEXELEMENT # BLOCK setting
R
setSrcRef
ObjectReference
SP FLEXELEMENT # BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef1
ORG
FLEXELEMENT # +IN setting
R
setSrcRef
ObjectReference
SP FLEXELEMENT # +IN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
FLEXELEMENT # IN setting
R
setSrcRef
ObjectReference
SP FLEXELEMENT # IN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
FlxLgcGAPC1
LDevice inst:
Gen
UR element:
FlexLogic
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Health
ENS
FLEXLOGIC ERR TOKEN self-test
R
stVal
ENUMERATED
ST FLEXLOGIC ERR TOKEN, 1 (Ok)
when operand is Off, 3 (Alarm)
when operand is On
R
Ind
ξ
SPS
Concatenation of value of VIRTUAL OUTPUT
ξ
ID + “ On (VO
ξ
) operand value
R
LNName:
DigElGAPC#
LDevice inst:
Gen
UR element:
Digital Element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...