3-70
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.44 Sensitive directional power (Sen)
This element is instantiated in the following products: C60, D60, F60, G30, G60, L90, M60, N60.
Table 3-65: Sensitive directional power general data objects
RstA
WYE
Restraint currents
R
net
CMV
R
net.instCVal
Vector
MX
R
net.instCVal.mag
.f
FLOAT32
RGF# RESTR Igr magnitude, in
primary amps
R
net.cVal
Vector
MX
R
net.cVal.mag.f
FLOAT32
RGF# RESTR Igr magnitude, in
primary amps, with deadband
R
net.units
Unit
CF
R
net.units.SIUnit
ENUMERATED
5, the code for amps
R
net.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
net.db
INT32U
CF RgDifPDIF#.RstA.net.db
R/W/C
net.zeroDb
INT32U
CF
R
BlkRef
γ
ORG
RESTD GND FT# BLOCK for setting group
γ
R
setSrcRef
ObjectReference
SP RESTD GND FT# BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
SenPDOP#
LDevice inst:
Prot
UR element:
Sensitive Directional Power element # core functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
DIR POWER # PKP operand, which becomes
On when either stage 1 or stage 2 of this
element has picked up
R
general
BOOLEAN
ST DIR POWER # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element can be connected/configured
to look forward or backward.
R
Op
ACT
DIR POWER # OP operand
R
general
BOOLEAN
ST DIR POWER # OP
R
Dpo
SPS
DIR POWER # DPO operand, which is the
inverse of DIR POWER OP
R
stVal
BOOLEAN
ST DIR POWER # DPO
R
TotW
MV
DIRECTIONAL POWER # 3-PHASE, in primary
watts
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
DIRECTIONAL POWER # 3
φ
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
DIRECTIONAL POWER # 3
φ
, deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
38, the code for primary watts (J/s)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF SenPDOP#.TotW.db
R/W/C
zeroDb
INT32U
CF
3-phase power cut-off level in percent
multiplied by 1000
R
BlkRef
γ
ORG
DIR POWER # BLK setting for setting group
γ
R
setSrcRef
ObjectReference
SP DIR POWER # BLK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
RgDifPDIF#
LDevice inst:
Prot
UR element:
Restricted Ground Fault # function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...