UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.48 Trip bus (TrBus)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-71: Trip bus data objects
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
DIFF 5TH HARM I
θ
d magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
DIFF 5TH HA
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF PctDifPDIF#.DifA5thH.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA
WYE
Phase restraint currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
REST PHASOR I
θ
r magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
REST PHASOR
UR range -180...+180 converted to 0...360
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
REST PHASOR I
θ
r magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
REST PHASOR
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF PctDifPDIF#.RstA.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
BlkRef
γ
ORG
PERCENT DIFF BLOCK for setting group
γ
R
setSrcRef
ObjectReference
SP PERCENT DIFF BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
TrBusPTRC#
LDevice inst:
Prot
UR element:
Trip Bus element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
TRIP BUS # OP operand, which becomes On
when any input is On, and the element is
not blocked
R
general
BOOLEAN
ST TRIP BUS # OP
R
Str
ACD
TRIP BUS # PKP operand, which indicates
that Op operates when delay expires
R
general
BOOLEAN
ST TRIP BUS # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
InRef
αα
ORG
TRIP BUS # INPUT
α
setting
R
setSrcRef
ObjectReference
SP TRIP BUS # INPUT
α
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
PctDifPDIF1
LDevice inst:
Prot
UR element:
Transformer Percent Differential function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...