CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-91
3
Pos
DPC
Breaker position control and status
R/Ctrl
stVal
CODED ENUM
ST
R
stSeld
BOOLEAN
ST
The controllable data status is “selected”
R
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
0 (pulse)
R
pulseConfig.onDur INT32U
2 ms (actually one pass)
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
1
R
ctlModel
CtlModels
CF XCBR# Pos ctlModel
R/W/C
sboTimeout
INT32U
CF XCBR# Pos sboTimeout
R/W/C
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF BREAKER # Toperate
R/C
BlkOpn
SPC
Blocks breaker open commands from all
sources including protection
R/Ctrl
stVal
BOOLEAN
ST
R
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
1 (persistent)
R
pulseConfig.onDur INT32U
0
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
0
R
ctlModel
CtlModels
CF XCBR# BlkOpn ctlModel
R/W/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
BlkCls
SPC
Blocks breaker close commands from all
sources
R/Ctrl
stVal
BOOLEAN
ST
R
pulseConfig
PulseConfig
CF
R
pulseConfig
.cmdQual
ENUMERATED
1 (persistent)
R
pulseConfig.onDur INT32U
0
R
pulseConfig
.offDur
INT32U
0
R
pulseConfig
.numPls
INT32U
0
R
ctlModel
CtlModels
CF XCBR# BlkCls ctlModel
R/W/C
sboTimeout
INT32U
CF
30000
R
sboClass
SboClasses
CF
0 (operate-once)
R
operTimeout
INT32U
CF
0
R
InRef1
ORG
BREAKER # OPEN setting
R
setSrcRef
ObjectReference
SP BREAKER # OPEN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
BREAKER # BLK OPEN setting
R
setSrcRef
ObjectReference
SP BREAKER # BLK OPEN
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef3
ORG
BREAKER # CLOSE setting
R
setSrcRef
ObjectReference
SP BREAKER # CLOSE
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
Bkr0XCBR#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...