2-48
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
3E7E
...Repeated for Field Shared Output 7
"
3E8B
...Repeated for Field Shared Output 8
"
3E98
...Repeated for Field Shared Output 9
"
3EA5
...Repeated for Field Shared Output 10
"
3EB2
...Repeated for Field Shared Output 11
"
3EBF
...Repeated for Field Shared Output 12
"
3ECC
...Repeated for Field Shared Output 13
"
3ED9
...Repeated for Field Shared Output 14
"
3EE6
...Repeated for Field Shared Output 15
"
3EF3
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 Modules)
All except B90,
L60
3F00
Field Unit RTD 1Name
0 to 1
---
1
F205
"RTD 1"
"
3F06
Field Unit RTD 1 Origin
0 to 24
---
1
F253
0 (None)
"
3F07
Field Unit RTD 1 Type
0 to 2
---
1
F259
0 (100 Ohm
Nickel)
"
3F08
...Repeated for Field Unit RTD 2
"
3F10
...Repeated for Field Unit RTD 3
"
3F18
...Repeated for Field Unit RTD 4
"
3F20
...Repeated for Field Unit RTD 5
"
3F28
...Repeated for Field Unit RTD 6
"
3F30
...Repeated for Field Unit RTD 7
"
3F38
...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 Modules)
All except B90,
L60
3F40
Field Unit Transducer 1 Name
0 to 1
---
1
F205
"TRD 1"
"
3F46
Field Unit Transducer 1 Origin
0 to 24
---
1
F253
0 (None)
"
3F47
Field Unit Transducer 1 Range
0 to 9
---
1
F246
6 (0...20mA)
"
3F48
Field Unit Transducer 1 Min Value
-9999.999 to
9999.999
---
0.001 F004
0
"
3F4A
Field Unit Transducer 1 Max Value
-9999.999 to
9999.999
---
0.001 F004
100000
"
3F4C
Field Unit Transducer 1 Units
---
---
---
F206
(none)
"
3F4F
...Repeated for Field Unit Transducer 2
"
3F5E
...Repeated for Field Unit Transducer 3
"
3F6D
...Repeated for Field Unit Transducer 4
"
3F7C
...Repeated for Field Unit Transducer 5
"
3F8B
...Repeated for Field Unit Transducer 6
"
3F9A
...Repeated for Field Unit Transducer 7
"
3FA9
...Repeated for Field Unit Transducer 8
Field Unit Identifiers (Read Only) (8 Modules)
All except B90,
L60
3FB8
Attached Field Unit 1 Serial Number
---
---
1
F205
(none)
"
3FBE
Attached Filed Unit 1 Port Number
---
---
1
F001
0
"
3FBF
Attached Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
"
3FC0
Field Unit 1 Status
0 to 4
---
1
F262
0 (Disabled)
"
3FC1
...Repeated for Field Unit 2
"
3FCA
...Repeated for Field Unit 3
"
3FD3
...Repeated for Field Unit 4
Products
Address Register name
Range
Units
Step
Format
Default
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...