background image

Operation:

When any thermostat calls for heat, the appropriate circu-

lator is energized and the isolated end switch (X and X) will start the
boiler.

Priority Operation:

When zone 2 is switched to the priority setting

and is actuated, all other zones will stop operation until zone 2 is sat-
isfied. When zone 2 is not switched to priority, all zones will operate
independently.

Priority Protection Operation:

When the priority switch is set to ON,

and  if  the  priority  zone  calls  continuously  for  more  than  one  hour,
power is returned to all the other zones, allowing each zone to function
independently.  Once  the  priority  zone  is  satisfied,  the  control’s  auto-
reset is activated and the priority zone is again allowed to have priority
for up to one hour starting from when it calls next.

Jumper Placement:

The jumper should be placed between terminals

ZC and ZR. Connect the isolated end switch to the aquastat control
on the boiler.

Power Input:

Connect 120 volt ac power input to terminals N and

H. Neutral wire to terminal N. Hot wire to terminal H.

Operation:

When any thermostat calls for heat, the boiler is given a

signal  to  start.  The  appropriate  circulator  is  energized  only  when  the
boiler temperature is above the set low limit.

Priority Operation:

When zone 2 is switched to the priority setting and is actu-

ated, all other zones will stop operation until zone 2 is satisfied. When zone 2 is
not switched to priority, all zones will operate independently.

Priority Protection Operation:

When the priority switch is set to ON,

and  if  the  priority  zone  calls  continuously  for  more  than  one  hour,
power is returned to all the other zones, allowing each zone to function
independently.  Once  the  priority  zone  is  satisfied,  the  control’s  auto-
reset is activated and the priority zone is again allowed to have priority
for up to one hour starting from when it calls next.

Jumper Placement:

REMOVE the jumper between terminals ZC and

ZR. Connect terminal ZC to ZC on the aquastat control. Connect ter-
minal ZR to ZR on the aquastat control. Confirm polarity is consistent
between boiler aquastat and switching relay.

Power Input:

Connect 120 volt ac power input to terminals N and H.

Neutral wire to terminal N. Hot wire to terminal H.

Cold Start Boiler

Application:

Tankless Coil Boiler Application:

(Alternative Wiring)

Instruction Sheet

SR502-4 Switching Relay

102-377

SUPERSEDES: December 20, 2013

EFFECTIVE: 

Jan

uary 

18

, 2017

Plant ID# 9300-2866

WARNING:

When using Alternative Wiring diagram, wiring instruc-

tions must be followed so power originates from the boiler aquastat.
Failure to follow these wiring instructions may result in a secondary
source  of  power  being  connected  to  the  boiler  that  may  activate  it
under certain circumstances, causing injury or death.

Specifications:

PRODUCT            NUMBER                INPUT

MAXIMUM

TYPE 1 ENCLOSURE

NUMBER            OF ZONES            VOLTAGE         COMBINED LOAD              WIDTH        HEIGHT        DEPTH
SR502-4          2 with Priority   120/60/1 VAC             15 amps

12

1

/

4

"  

   8"

3"

All circulator relay connections, including ZC/ZR, are rated 

1

/

3

hp (6 FLA, 36 LRA) at 120 VAC.

End switch connections are rated 24 VAC, 1 amp.

All thermostat connections supply a 24 VAC class 2 output.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This

device may not cause harmful interference, and (2) this device must accept any interference received, including

interference that may cause undesired operation.

WARNING: 

Wiring  connections  must  be  made  in  accordance  with  all

applicable electrical codes. Use copper wire only. 120 VAC wiring must have
a minimum temperature rating of 75°C. Failure to follow this instruction
can result in personal injury or death and/or property damage. 12-18 gauge
wire recommended for 120 VAC connections, 14-22 gauge wire for thermo-
stat connections, and 14-22 gauge wire for 24 VAC source connections.

NOTE:

Resistor (1K

Ω

1

2

W) may be needed

between 

W

and 

C

terminals.

Troubleshooting:
• Problem:

Digital thermostats do not work correctly when connected

to a switching relay.

• Solution:

Some thermostats are a “Power Stealing” type which means

they are powered by the switching relay with just 2 wires (

R

W

). A

resistor may be needed in order to have the thermostat work properly.
This resistor should be placed between the 

W

C

(

common

) termi-

nals of the switching relay. If the thermostat manufacturer does not
supply a resistor, a 1000 ohm ½ watt resistor has proven to work with
most models and is readily available at electronic supply outlets (e.g.
Radio  Shack).  If  the  thermostat  is  battery  powered,  then  check  that
the batteries are fresh and installed correctly.

• Problem:

No heat in a zone or room of building.

• Solution: 

LED diagnostic  lights  will  help  find  a  component  that  is

not working properly. The green LED should always be on, indicating
that power is connected and the solid-state fuse is good. When there
is a call for heat, the red LED will come on indicating power to the
zone circulator. This indicates the thermostat is working correctly. If
the red LED does not come on, then check the thermostat and ther-
mostat wiring for errors.

For  information  on  Taco’s  Switching  Relays  (SR)
including  catalog  sheet,  instruction  sheets,  Visio
stencils  and  our  highly  praised  Zone  Controls
Wiring Guide, scan the QR code to the left or go to
our website: http://www.TacoComfort.com.

Reviews: