CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-55
3
neut
CMV
R
neut.instCVal
Vector
MX
R
neut.instCVal.mag
.f
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps
R
neut.instCVal.ang
.f
FLOAT32
IG DIFF. CU
UR range -180...+180 converted to 0...360
R
neut.cVal
Vector
MX
R
neut.cVal.mag.f
FLOAT32
IG DIFF. CURRENT magnitude, in
primary amps, with deadband
R
neut.cVal.ang.f
FLOAT32
IG DIFF. CU
UR range -180...+180 converted to 0...360
R
neut.units
Unit
CF
R
neut.units.SIUnit
ENUMERATED
5, the code for amps
R
neut.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
neut.db
INT32U
CF LinDfPDIF1.DifAClc.neut.db
R/W/C
neut.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA
WYE
Restraint currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
I
θ
RESTR. CURRENT magnitude, in
primary amps
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
I
θ
RESTR. CURRENT magnitude, in
primary amps, with deadband
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF LinDfPDIF1.DifAClc.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46
R
neut
CMV
R
neut.instCVal
Vector
MX
R
neut.instCVal.mag
.f
FLOAT32
IG RESTR. CURRENT magnitude, in
primary amps
R
neut.cVal
Vector
MX
R
neut.cVal.mag.f
FLOAT32
IG RESTR. CURRENT magnitude, in
primary amps, with deadband
R
neut.units
Unit
CF
R
neut.units.SIUnit
ENUMERATED
5, the code for amps
R
neut.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
neut.db
INT32U
CF LinDfPDIF1.DifAClc.neut.db
R/W/C
neut.zeroDb
INT32U
CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
InRef001
ORG
CHNL ASYM COMP setting
R
setSrcRef
ObjectReference
SP CHNL ASYM COMP setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef9
ORG
BLOCK GPS TIME REF setting
R
LNName:
LinDfPDIF1
LDevice inst:
Prot
UR element:
Line Differential element (ANSI 87L) phase and general
functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...