CHAPTER 3: IEC 61850 COMMUNICATION
SCL LOG MESSAGES
UR SERIES – COMMUNICATIONS GUIDE
3-151
3
ERROR: InRef=<DAI value> in DO$DA <DAI flattened name> for LN <data attribute>
This message is logged when the inRef is referring to anything other than BOOLEAN, FLOAT, or INT32.
check_local_inref_all failed
This message is logged when inrefs validation fails for the local IED.
Data types already created for this SCL file. Cannot create again.
This message is logged when data in the CID file is such that it invokes duplicate creation of datatypes.
Error generating type name for LNodeType id=<lnType id>
This message is logged when unable to create LNType.
SCL ERROR: DAType id=<type id> not found
This message is logged when unable to locate the data attribute type in the CID file.
SCL ERROR: Can't add type definition for BDA Struct type=<type>
This message is logged when unable to add the type definition of base data attribute.
EnumType <type> could not be found
This message is logged when unable to find the enumeration type in the CID file.
INT64 not supported on this platform
This message is logged when a 64-bit basic type is detected in the CID file.
INT64U not supported on this platform
This message is logged when an unsigned 64-bit basic type is detected in the CID file.
bType=<btype> is not recognized
This message is logged when an unrecognized basic type is found.
SDO type <type> cannot be found
This message is logged when unable to find the SDO type in the CID file.
ERROR adding type definitions for DO=<data object>
This message is logged when unable to add the data object definition due to errors in the configuration of CID file.
Cannot find DOType=<data object type> for DO=<data object name>
This message is logged when the DOtype cannot be found in the CID file.
ERROR adding SGCB
This message is logged when an error is found in setting group control block.
scl2_datatype_create FAILED for LNodeType id=<logical node id>
This message is logged when lnType cannot be created.
Number of RUNTIME_TYPE elements (<number of runtime type>) exceeds maximum (<maximum number of
runtime types). Cannot create type for LNodeType id=<logical node>
RUNTIME type elements are data attributes.
This message is logged when a new runtime type could not be created since the maximum allowed limit is reached.
Содержание UR series
Страница 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Страница 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Страница 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Страница 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Страница 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...