DPR-145 User Manual                                                                           V-3.0 

(14.09.2016) 

 

-1- 

 

  

 

  

DPR-145  

TEMPERATURE 
PROTECTION RELAY 

 

PT100 INPUTS: 4 

 

RELAY OUTPUTS: 4 

 

RS-485 MODBUS PORT 

 

UNIVERSAL SUPPLY 

 

 

DPR-145 is a precision unit designed for the 
temperature protection of dry type or resin filled 
MV transformers. The unit offers a high degree of 
protection against electromagnetic disturbances. 

The unit has 4 temperature inputs of PT100 type. 
Three of them are used for the transformer 
protection. The fourth input may be used as core 
temperature protection or ambient temperature 
monitoring. 

Alarm and trip levels of the unit are independently 
adjustable for first 3 sensors and the fourth 
sensor input. 

Alarm levels are adjusted using the program 
mode. If no operation is performed, then the unit 
will exit program mode in 3 minutes. 

The unit offers a cable compensation function in 
order to prevent long cables from impairing the  
measurement precision. 

The unit has 4 dry contact relay outputs rated 6A. 

FAN

: provides cooler fan control 

TRIP

: high temperature failure relay 

ALARM

: pre-alarm relay 

FAULT

: sensor or internal failure indicator 

The unit offers an automatic self test feature. The 
self test consists on the verification of sensor 
inputs and internal memory integrity. 

The standard isolated RS-485 MODBUS RTU 
communication port is not affected by ground 
potential differences and allows safe transfer of 
information to remote management and 
automation systems. 

The supply input is isolated from sensor 
connections.   

 

1 degrees C measurement precision 

4 x PT100 analog inputs 

Allows cable length compensation 

Automatic detection of sensor failures 

Automatic and manual self test 

4 x relay outputs, 5A/250Vac 

Fully isolated RS-485 serial port 

MODBUS-RTU communication 

Recording of maximum temperatures 

Front panel programmable  

2 alarm thresholds for channels 1-2-3 

2 alarm thresholds for channel 4 

Easy to read, 3 digit 14mm led display 

Supply voltage range: 19-400VDC (85-305VAC) 

Reduced panel depth, easy to install 

Wide operating temperature range, -

20 to +70°C 

Sealed front panel (IP65 with gasket) 

2 part connection system

 

 

  

 

   

 

 

DESCRIPTION

 

FEATURES

 

Summary of Contents for DPR-145

Page 1: ...6A FAN provides cooler fan control TRIP high temperature failure relay ALARM pre alarm relay FAULT sensor or internal failure indicator The unit offers an automatic self test feature The self test co...

Page 2: ...ranty voids if the unit is open Fuse must be connected to the power supply input Fuses must be of fast type with a maximum rating of 6A Disconnect all power before working on equipment When the unit i...

Page 3: ...FUNCTIONS 3 DISPLAYS 3 1 MODES OF OPERATION 4 ALARMS 4 1 ALARM MENU 5 PROGRAMMING 5 1 ENTERING THE PROGRAM MODE 5 2 LAMP TEST 5 3 RELAY TEST 5 4 MODIFYING PROGRAM PARAMETERS 5 5 PROGRAM PARAMETER LIST...

Page 4: ...ning Make electrical connections with plugs removed from sockets then place plugs to their sockets Otherwise sockets may get damaged Make sure not overloading relay outputs Use additional contactors i...

Page 5: ...DPR 145 User Manual V 3 0 14 09 2016 5 Panel Cutout Required Panel Depth 1 1 FRONT REAR PANELS 1 2 MECHANICAL INSTALLATION...

Page 6: ...ower supply input in close proximity of the unit Fuses must be of fast type with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75mm2 AWG18 Fo...

Page 7: ...previous channel or increase related value program mode Switch to the next channel or decrease related value program mode IF HELD PRESSED DURING 5 SEC will be displayed and all Trip Fault and Alalrm...

Page 8: ...side 1 2 3 4 indicate the related channel number SCAN Displays channel temperatures switches to the next channel every 5 seconds AUTO Displays the temperature of the highest channel MAN Displays the t...

Page 9: ...will turn off and normal operating mode will be resumed ALARM CODE DESCRIPTION SHORT CIRCUIT Indicates a short circuit on the related channel The FAULT led and the related channel led turns on Cables...

Page 10: ...will turn on The alarm code will be displayed Different alarm types fault trip alarm may be scrolled with the MODE pushbutton If the related type of alarm has not occurred on any channel then wil be d...

Page 11: ...onds PGM will be displayed Every depression to the MODE button will switch to the next parameter Related parameter name is displayed When the name of the parameter to be modified is displayed hold pre...

Page 12: ...the screen Arrow down button deactivates the relay output and displays 0 on the screen Mode button will switch to next relay or parameter display 5 2 LAMP TEST When exiting the PROGRAM mode the unit m...

Page 13: ...ster you can hold arrow buttons pressed When MODE button is pressed the parameter value is recorded and the next parameter name is displayed DISPLAY DESCRIPTION MIN MAX PT100 CABLE SECTION PT100 cable...

Page 14: ...he relay The value of 0 deactivates it 0 1 ALARM PARAMETER Adjusts High Temperature Alarm limit values of each channel 0 295 TRIP PARAMETER Adjusts High Temperature Trip values of channels 5 300 FAN C...

Page 15: ...600 baud 7 56000 baud 3 14400 baud 8 57600 baud 4 19200 baud 9 115200 baud 0 9 MODBUS NODE ADDRESS nod This parameter defines the address of the unit in a Modbus network Each device in the same networ...

Page 16: ...tructure contain multiple registers Detailed description about the MODBUS protocol is found in the document Modicon Modbus Protocol Reference Guide This document may be downloaded at www modbus org do...

Page 17: ...4 Channel 4 Trip temperature C 16 BIT R W unsigned word 1 8 Fan Channel Fan relay channel selection 16 BIT R W unsigned word 1 9 Fan ON Fan Turn On Temperature C 16 BIT R W unsigned word 1 10 Fan OFF...

Page 18: ...3 registers ADDRESS BIT R W DESCRIPTION 20488 0 R O Alarm Relay Status 1 R O Trip Relay Status 2 R O Fan Relay Status 3 R O Fault Relay Status 4 15 R O Not used 20489 0 R O Channel 1 Alarm 1 R O Chan...

Page 19: ...Measuring Inputs 4 x PT100 3 terminals Accuracy 1 1 digit Measurement Range 40 to 250 C Power Consumption 4 VA Relay Outputs 5A 250V AC Serial Port Signal type RS 485 Protocol Modbus RTU Data Rate 240...