CHAPTER 8: DNP COMMUNICATIONS
DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL
8–5
Implementation Table Notes:
1.
For this object, the quantity specified in the request must be exactly 1 as there is only
one instance of this object defined in the relay.
2.
All static input data known to the relay is returned in response to a request for Class 0.
This includes all objects of type 1 (Binary Input) and type 30 (Analog Input).
3.
The point tables for Binary Input and Analog Input objects contain a field which
defines which event class the corresponding static data has been assigned to.
4.
For this object, the qualifier code must specify an index of 7 only.
5.
Warm Restart (function code 14) is supported although it is not required by the DNP
level 2 specification.
6.
Object 1 Variation 1 always indicates ON LINE for all points.
50
1
Time and Date
1, 2
07 (Note 1)
129
07
60
1
Class 0 Data (Note 2)
1
06
129
60
2
Class 1 Data (Note 3)
1
06, 07, 08
129
60
3
Class 2 Data (Note 3)
1
06, 07, 08
129
60
4
Class 3 Data (Note 3)
1
06, 07, 08
129
80
1
Internal Indications
2
00 (Note 4)
129
No object - Cold Start
13
No object - Warm Start (Note
5)
14
No object - enable
unsolicited (parsed only)
20
No object - disable
unsolicited (parsed only)
21
No object - Delay
Measurement
23
Table 8–1: DNP Implementation Table (Continued)
OBJECT
REQUEST
RESPONSE
OBJ VAR
DESCRIPTION
FUNC
CODES
QUAL CODES
(hex)
FUNC
CODES
QUAL
CODES
(hex)
1, 2, 3, 4, 5, 6: see the IMPLEMENATION TABLE NOTES on the following page.