CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–53
CALCU-
LATION
PARAMETERS
1030
Current Demand Calculation Type
0 to 2
1
---
F28
0 = Thermal
Exponential
1031
Current Demand Time Interval
5 to 180
1
minutes
F1
30 min
1032
Power Demand Calculation Type
0 to 2
1
---
F28
0 = Thermal
Exponential
1033
Power Demand Time Interval
5 to 180
1
minutes
F1
30 min
1034
Energy Cost Per kWh
1 to 50000
1
¢ x 0.01
F1
10.00 ¢
1035
Extract Fundamental
0 to 1
1
---
F11
0=DISABLE
1036
Reserved
1037
Reserved
CLEAR DATA
1038
Clear Energy Values
0 to 1
1
---
F31
0 = NO
1039
Clear Max Demand Values
0 to 1
1
---
F31
0 = NO
103A
Clear Min/Max Current Values
0 to 1
1
---
F31
0 = NO
103B
Clear Min/Max Voltage Values
0 to 1
1
---
F31
0 = NO
103C
Clear Min/Max Power Values
0 to 1
1
---
F31
0 = NO
CLEAR DATA
continued
103D
Clear Max THD Values
0 to 1
1
---
F31
0 = NO
103E
Clear Pulse Input Values
0 to 1
1
---
F31
0 = NO
103F
Clear Event Record
0 to 1
1
---
F31
0 = NO
1040
Clear All Demand Values
0 to 1
1
---
F31
0 = NO
1041
Clear Frequency Values
0 to 1
1
---
F31
0 = NO
1042
Reserved
1043
Reserved
DNP
1044
DNP Port
0 to 3
1
---
F47
0 = NONE
1045
DNP Slave Address
0 to 255
1
---
F1
0
1046
DNP Turnaround Time
0 to 100
10
ms
F1
10 ms
TARIFF
1047
Tariff Period 1 Start Time
0 to 1439
1
minutes
F1
0 min.
1048
Tariff Period 1 Cost per kWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
1049
Tariff Period 2 Start Time
0 to 1439
1
minutes
F1
0 min.
104A
Tariff Period 2 Cost per kWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
104B
Tariff Period 3 Start Time
0 to 1439
1
minutes
F1
0 min.
104C
Tariff Period 3 Cost per kWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
104D
Reserved
104E
Reserved
104F
Reserved
Table 7–10: PQM Memory Map (Sheet 37 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only