CHAPTER 8: DNP COMMUNICATIONS
DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL
8–13
31
02FE
Phase B Real Power
1000ths of
nominal
20 units
F4
3
32
0300
Phase B Reactive Power
1000ths of
nominal
20 units
F4
3
33
0302
Phase B Apparent
Power
1000ths of
nominal
20 units
F3
3
34
0304
Phase B Power Factor
%
10 units
F2
3
35
0305
Phase C Real Power
1000ths of
nominal
20 units
F4
3
36
0307
Phase C Reactive Power
1000ths of
nominal
20 units
F4
3
37
0309
Phase C Apparent
Power
1000ths of
nominal
20 units
F3
3
38
030B
Phase C Power Factor
%
10 units
F2
3
39
0400
Phase A Current
Demand
1000ths of
nominal
20 units
F1
3
40
0401
Phase B Current
Demand
1000ths of
nominal
20 units
F1
3
41
0402
Phase C Current
Demand
1000ths of
nominal
20 units
F1
3
42
0403
Neutral Current
Demand
1000ths of
nominal
20 units
F1
3
43
0404
3 Phase Real Power
Demand
1000ths of
nominal
20 units
F4
3
44
0406
3 Phase React Power
Demand
1000ths of
nominal
20 units
F4
3
45
0408
3 Phase Apparent
Power Demand
1000ths of
nominal
20 units
F3
3
46
0440
Frequency
0.01x Hz
.05 Hz
F1
1
47
0458
Main/Alternate Analog
Input
Unit varies
-- 32 bits
10
F3
2
48
0470
Ia Crest Factor
0.001 x CF
50
F1
-
49
0471
Ib Crest Factor
0.001 x CF
50
F1
-
50
0472
Ic Crest Factor
0.001 x CF
50
F1
-
Table 8–4: Point List for Analog Input/Output Change (Sheet 3 of 9)
POINT
MOBUS
REG
DESCRIPTION
UNIT /
VALUE
DEADBAND
FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table