7–62
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
CURRENT/
VOLTAGE
ALARMS
1126
Phase Overcurrent Activation
0 to 1
1
---
F115
0=AVERAGE
1127
Detect I/V Alarms Using Percentage
0 to 1
1
---
F31
0=NO
1128
Phase Undercurrent Relay
0 to 4
1
---
F29
0=OFF
1129
Phase Undercurrent Level in Amps
1 to 12000
1
A
F1
100 A
112A
Phase Undercurrent Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
112B
Phase Overcurrent Relay
0 to 4
1
---
F29
0=OFF
112C
Phase Overcurrent Level in Amps
1 to 12000
1
A
F1
100 A
112D
Phase Overcurrent Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
112E
Neutral Overcurrent Relay
0 to 4
1
---
F29
0=OFF
112F
Neutral Overcurrent Level in Amps
1 to 12000
1
A
F1
100 A
1130
Neutral Overcurrent Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1131
Undervoltage Relay
0 to 4
1
---
F29
0=OFF
1132
Undervoltage Level in Volts
20 to
65000
1
V
F1
100 V
1133
Undervoltage Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1134
Phases Req’d for Operation of U/V
0 to 2
1
---
F30
0=ANY ONE
1135
Detect U/V Below 20V
0 to 1
1
---
F11
0=DISABLE
1136
Overvoltage Relay
0 to 4
1
---
F29
0=OFF
1137
Overvoltage Level in Volts
1 to 65000
1
V
F1
100 V
1138
Overvoltage Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1139
Phases Req’d for Operation of O/V
0 to 2
1
---
F30
0=ANY ONE
113A
Phase Current Unbalance Relay
0 to 4
1
---
F29
0=OFF
113B
Phase Current Unbalance Level
1 to 100
1
%
F1
10%
113C
Phase Current Unbalance Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
113D
Voltage Unbalance Relay
0 to 4
1
---
F29
0=OFF
113E
Voltage Unbalance Level
1 to 100
1
%
F1
10%
113F
Voltage Unbalance Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1140
Voltage Phase Reversal Relay
0 to 4
1
---
F29
0=OFF
1141
Voltage Phase Reversal Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1142
Detect Undercurrent When 0A
0 to 1
1
---
F31
0=NO
1143
Phase Undercurrent Level in % of CT
1 to 100
1
%
F1
100%
1144
Phase Overcurrent Level in % of CT
1 to 150
1
%
F1
100%
1145
Neutral Overcurrent Level in % of CT
1 to 150
1
%
F1
100%
1146
Undervoltage Level in % of VT
20 to 100
1
%
F1
100%
1147
Overvoltage Level in % of VT
20 to 100
1
%
F1
150%
Table 7–10: PQM Memory Map (Sheet 46 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...