8–16
PQM POWER QUALITY METER – INSTRUCTION MANUAL
DNP 3.0 PROTOCOL
CHAPTER 8: DNP COMMUNICATIONS
90
030C
3 Phase Real Power -
Minimum
1000ths of
nominal W
1 unit
F4
3
91
030E
3 Phase Reactive Power
Minimum
1000ths of
nominal
kvar
1 unit
F4
3
92
0310
3 Phase Apparent
Power Minimum
1000ths of
nominal VA
1 unit
F3
3
93
0312
3 Phase Power Factor -
Minimum
%
1 unit
F2
3
94
0313
3 Phase Real Power -
Maximum
1000ths of
nominal
1 unit
F4
3
95
0315
3 Phase Reactive Power
Maximum
1000ths of
nominal
1 unit
F4
3
96
0317
3 Phase Apparent
Power Maximum
1000ths of
nominal
1 unit
F3
3
97
0319
3 Phase Power Factor -
Maximum
%
1 unit
F2
3
98
031A
Phase A Real Power -
Minimum
1000ths of
nominal
1 unit
F4
3
99
031C
Phase A Reactive Power
Minimum
1000ths of
nominal
1 unit
F4
3
100
031E
Phase A Apparent
Power Minimum
1000ths of
nominal
1 unit
F3
3
101
0220
Phase A Power Factor -
Minimum
%
1 unit
F2
3
102
0321
Phase A Real Power -
Maximum
1000ths of
nominal
1 unit
F4
3
103
0323
Phase A Reactive Power
Maximum
1000ths of
nominal
1 unit
F4
3
104
0325
Phase A Apparent
Power Maximum
1000ths of
nominal
1 unit
F3
3
105
0327
Phase A Power Factor
Maximum
%
1 unit
F2
3
106
0328
Phase B Real Power
Minimum
1000ths of
nominal
1 unit
F4
3
107
032A
Phase B Reactive Power
Minimum
1000ths of
nominal
1 unit
F4
3
Table 8–4: Point List for Analog Input/Output Change (Sheet 6 of 9)
POINT
MOBUS
REG
DESCRIPTION
UNIT /
VALUE
DEADBAND
FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...