CHAPTER 4: PROGRAMMING
S1 PQM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–17
in the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint. Phase to neutral levels are used regardless of the
VT wiring.
•
Vb OVERVOLTAGE TRIG LEVEL:
Once the phase B voltage equals or increases above
this setpoint value, the trace memory is triggered and data on all inputs are captured
in the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint. Phase to neutral levels are used regardless of the
VT wiring.
•
Vc OVERVOLTAGE TRIG LEVEL:
Once the phase C voltage equals or increases above
this setpoint value, the trace memory is triggered and data on all inputs are captured
in the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint. Phase to neutral levels are used regardless of the
VT wiring.
•
Va UNDERVOLTAGE TRIG LEVEL:
Once the phase A voltage is equal to or less than this
setpoint value, the trace memory is triggered and data on all inputs are captured in
the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
Vb UNDERVOLTAGE TRIG LEVEL:
Once the phase B voltage is equal to or less than this
setpoint value, the trace memory is triggered and data on all inputs are captured in
the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
Vc UNDERVOLTAGE TRIG LEVEL:
Once the phase C voltage is equal to or less than this
setpoint value, the trace memory is triggered and data on all inputs are captured in
the buffer. The number of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
SWITCH INPUT A TRIG:
If the setpoint is set to OPEN-TO-CLOSED, the trace memory is
triggered and data on all inputs are captured in the buffer on a switch A close
transition. If the setpoint is set to
CLOSED-TO-OPEN
, the trace memory is triggered and
data on all inputs are captured in the buffer on a switch A open transition. The number
of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
SWITCH INPUT B TRIG:
If the setpoint is set to
OPEN-TO-CLOSED
, the trace memory
will be triggered and data on all inputs are captured in the buffer on a switch B close
transition. If the setpoint is set to
CLOSED-TO-OPEN
, the trace memory is triggered and
data on all inputs are captured in the buffer on a switch B open transition. The number
of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
SWITCH INPUT C TRIG:
If the setpoint is set to
OPEN-TO-CLOSED
, the trace memory is
triggered and data on all inputs are captured in the buffer on a switch C close
transition. If the setpoint is set to
CLOSED-TO-OPEN
, the trace memory is triggered and
data on all inputs are captured in the buffer on a switch C open transition. The number
of cycles captured depends on the value specified in the
TRACE MEMORY USAGE
setpoint.
•
SWITCH INPUT D TRIG:
If the setpoint is set to
OPEN-TO-CLOSED
, the trace memory is
triggered and data on all inputs will be captured in the buffer on a switch D close
transition. If the setpoint is set to CLOSED-TO-OPEN, the trace memory is triggered and