CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–65
PULSE
INPUT
ALARMS
11A8
Pulse Input 1 Relay
0 to 4
1
---
F29
0=OFF
11A9
Pulse Input 1 Level
1 to 65000
1
---
F1
100
11AA
Pulse Input 1 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11AB
Reserved
to
↓
↓
↓
↓
↓
↓
11AF
Reserved
MISC.
ALARMS
11B0
Serial COM1 Failure Alarm Delay
5 to 61***
1
s
F1
61=OFF
11B1
Serial COM2 Failure Alarm Delay
5 to 61***
1
s
F1
61=OFF
11B2
Clock Not Set Alarm
0 to 1
1
---
F11
1 = ENABLE
11B3
Data Log 1 Percentage Full Alarm Level
50 to
101***
1
s
F1
101=OFF
11B4
Data Log 2 Percentage Full Alarm Level
50 to
101***
1
s
F1
101=OFF
11B5
Reserved
11B6
Reserved
11B7
Reserved
PULSE
INPUT
ALARMS
11B8
Pulse Input 2 Relay
0 to 4
1
---
F29
0=OFF
11B9
Pulse Input 2 Level
1 to 65000
1
---
F1
100
11BA
Pulse Input 2 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11BB
Pulse Input 3 Relay
0 to 4
1
---
F29
0=OFF
11BC
Pulse Input 3 Level
1 to 65000
1
---
F1
100
11BD
Pulse Input 3 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11BE
Pulse Input 4 Relay
0 to 4
1
---
F29
0=OFF
11BF
Pulse Input 4 Level
1 to 65000
1
---
F1
100
11C0
Pulse Input 4 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11C1
Totalized Pulse Input Relay
0 to 4
1
---
F29
0=OFF
11C2
Totalized Pulse Input Level
1 to 65000
1
---
F1
100
11C3
Totalized Pulse Input Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11C4
Reserved
to
↓
↓
↓
↓
↓
↓
11C7
Reserved
Table 7–10: PQM Memory Map (Sheet 49 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...