7–60
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
PULSE
OUTPUT
10F0
Positive kWh Pulse Output Relay
0 to 4
1
---
F29
0=OFF
10F1
Positive kWh Pulse Output Interval
1 to 65000
1
kWh
F1
100 kWh
10F2
Negative kWh Pulse Output Relay
0 to 4
1
---
F29
0=OFF
10F3
Negative kWh Pulse Output Interval
1 to 65000
1
kWh
F1
100 kWh
10F4
Positive kvarh Pulse Output Relay
0 to 4
1
---
F29
0=OFF
10F5
Positive kvarh Pulse Output Interval
1 to 65000
1
kvarh
F1
100 kvarh
10F6
Negative kvarh Pulse Output Relay
0 to 4
1
---
F29
0=OFF
10F7
Negative kvarh Pulse Output Interval
1 to 65000
1
kvarh
F1
100 kvarh
10F8
kVAh Pulse Output Relay
0 to 4
1
---
F29
0=OFF
10F9
kVAh Pulse Output Interval
1 to 65000
1
kVAh
F1
100 kVAh
10FA
Pulse Output Width
100 to
2000
10
ms
F1
100 ms
10FB
Serial Pulse Relay Interval
100 to
10000
100
ms
F1
100 ms
10FC
Reserved
PULSE
INPUT
10FD
Pulse Input Units 1
st
and 2
nd
char.
---
---
ASCII
F10
“ U”
10FE
Pulse Input Units 3
rd
and 4
th
char.
---
---
ASCII
F10
“ni”
10FF
Pulse Input Units 5
th
and 6
th
char.
---
---
ASCII
F10
“ts”
1100
Pulse Input Units 7
th
and 8
th
char.
---
---
ASCII
F10
““
1101
Pulse Input Units 9
th
and 10
th
char.
---
---
ASCII
F10
““
1102
Pulse Input 1 Value
0 to 65000
1
Units
F1
1
1103
Pulse Input 2 Value
0 to 65000
1
Units
F1
1
1104
Pulse Input 3 Value
0 to 65000
1
Units
F1
1
1105
Pulse Input 4 Value
0 to 65000
1
Units
F1
1
1106
Pulse Input Total
0 to 10
1
---
F43
9 = 1+2+3+4
1107
Reserved
ALARM
RELAY
1108
Alarm Relay Operation
0 to 1
1
---
F17
0 = NON-
FAILSAFE
1109
Alarm Relay Activation
0 to 1
1
---
F18
0 = UNLATCHED
110A
Reserved
to
↓
↓
↓
↓
↓
↓
110F
Reserved
Table 7–10: PQM Memory Map (Sheet 44 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only