CHAPTER 4: PROGRAMMING
S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–33
4.3.5
Pulse Output
FIGURE 4–17: Setpoints Page 2 – System Setup / Pulse Output
•
kWh / kvarh / kVAh PULSE OUTPUT RELAY:
Five pulse output parameters can be
assigned to the alarm or auxiliary relays. They are Positive kWh, Negative kWh,
Positive kvarh, Negative kvarh, and kVAh. Enter the desired relay to which each
parameter is assigned. Select OFF if a particular output parameter is not required.
•
KWh / kvarh / kVAh PULSE OUTPUT INTERVAL:
Enter the interval for the appropriate
quantity at which the relay pulse will occur. The pulse width is set by the PULSE WIDTH
setpoint described below. If the pulse interval is set to 100 kWh, one pulse will indicate
that 100kWh has been accumulated.
]] SETPOINTS
]] S2 SYSTEM SETUP
]] SETPOINTS
]] S3 OUTPUT RELAYS
SETPOINT
] CURRENT/VOLTAGE
] CONFIGURATION
] SWITCH INPUT D
]
POS kWh PULSE OUTPUT
RELAY: OFF
POS kWh PULSE OUTPUT
INTERVAL:
100 kWh
Range: ALARM, AUX1, AUX2, AUX3, OFF
NEG kWh PULSE OUTPUT
RELAY: OFF
NEG kWh PULSE OUTPUT
INTERVAL:
100 kWh
POS kvarh PULSE OUTPUT
RELAY: OFF
POS kvarh PULSE OUTPUT
INTERVAL:
100 kvarh
NEG kvarh PULSE OUTPUT
RELAY: OFF
NEG kvarh PULSE OUTPUT
INTERVAL:
100 kvarh
kVAh PULSE OUTPUT
RELAY: OFF
kVAh PULSE OUTPUT
INTERVAL:
100 kVAh
PULSE WIDTH:
100 ms
Range: 1 to 65000; Step: 1 kWh
] PULSE OUTPUT
]
Range: ALARM, AUX1, AUX2, AUX3, OFF
Range: 1 to 65000; Step: 1 kWh
Range: 1 to 65000; Step: 1 kvarh
Range: 1 to 65000; Step: 1 kvarh
Range: 1 to 65000; Step: 1 kVAh
Range: 100 to 2000; Step: 10 ms
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: ALARM, AUX1,
AUX2, AUX3, OFF
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...