7–18
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
Commands (Holding Registers) Addresses - 0080-00EF
COMMANDS
0080
Command Function Code
5
---
---
F1
5
0081
Command Operation Code
1 to 35
1
---
F7
0
0082
Command Data 1
0 to 65535
1
---
*
0
0083
Command Data 2
0 to 65535
1
---
F31
0
0084
Command Data 3
0 to 65535
1
---
F8
0
0085
Command Data 4
0 to 65535
1
---
F8
0
0086
Command Data 5
0 to 65535
1
---
F8
0
0087
Command Data 6
0 to 65535
1
---
F8
0
0088
Command Data 7
0 to 65535
1
---
F8
0
0089
Command Data 8
0 to 65535
1
---
F8
0
008A
Command Data 9
0 to 65535
1
---
F8
0
008B
Command Data 10
0 to 65535
1
---
F8
0
008C
Command Data 11
0 to 65535
1
---
F8
0
008D
Reserved
to
↓
00EF
Reserved
Broadcast Command (Holding Registers) Addresses - 00F0-00FF
BROADCAST
COMMAND
00F0
Time Hours/Minutes
0 to 65535
1
hr/min
F22
N/A
00F1
Time Seconds
0 to 59999
1
ms
F23
N/A
00F2
Date Month/Day
0 to 65535
1
---
F24
N/A
00F3
Date Year
0 to 59999
1
---
F25
N/A
00F4
Reserved
to
↓
00FF
Reserved
Table 7–10: PQM Memory Map (Sheet 2 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only