4–60
PQM POWER QUALITY METER – INSTRUCTION MANUAL
S5 TESTING
CHAPTER 4: PROGRAMMING
•
PHASE ANGLE
: The phase angle in this setpoint represents the phase shift from a unity
power factor. Enter the desired phase angle between the current and voltage. The
angle between the individual currents and voltages is fixed at 120°.
4.6.3
Analog
Outputs
Simulation
FIGURE 4–36: Setpoints Page 5 – Analog Output Simulation
•
SIMULATION
: Enter ON to switch from actual analog outputs to the programmed
simulated values. Set this setpoint OFF after simulation is complete.
•
SIMULATION ENABLED FOR
: Select the desired length of time that simulation will be
enabled. When the programmed time has elapsed, analog output simulation will turn
off. If unlimited is selected, simulated analog outputs will be used until simulation is
turned off via the simulation on/off setpoint or via the serial port or until control power
is removed from the PQM.
•
ANALOG OUTPUT 1/2/3/4
: Enter the percent analog output value to be simulated.
Whether the output is 0 to 1 mA, or 4 to 20 mA is dependent upon the option installed.
For example, alter the setpoints below:
S5 TESTING \ ANALOG OUTPUTS SIMULATION \ ANALOG OUTPUT 1:
50.0%
S5 TESTING \ ANALOG OUTPUTS SIMULATION \ SIMULATION:
ON
The output current level on analog output 1 will be 12 mA (4 to 20mA) or 0.5 mA (0 to 1mA).
]] SETPOINTS
]] S5 TESTING
] ANALOG OUTPUTS
] SIMULATION
SIMULATION:
OFF
SIMULATION ENABLED
FOR: 15 min
ANALOG OUTPUT 1:
OFF %
]] SETPOINTS
]] S1 PQM SETUP
SETPOINT
Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min
ANALOG OUTPUT 2:
OFF %
ANALOG OUTPUT 3:
OFF %
ANALOG OUTPUT 4:
OFF %
] TEST RELAYS & LEDS
]
] CURRENT/VOLTAGE
] SIMULATION
Range: 0.0 to 120.0, OFF; Step: 0.1%
Range: 0.0 to 120.0, OFF; Step: 0.1%
Range: 0.0 to 120.0, OFF; Step: 0.1%
Range: 0.0 to 120.0, OFF
Step: 0.1%
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...