7–78
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
F28
UNSIGNED INTEGER
DEMAND CALCULATION TYPE
FFFF
0 = Thermal Exponential
---
1 = Block Interval
---
2 = Rolling Interval
---
F29
UNSIGNED INTEGER
ALARM/CONTROL RELAY SELECTION
FFFF
0 = Off
---
1 = Alarm Relay
---
2 = Auxiliary Relay 1
---
3 = Auxiliary Relay 2
---
4 = Auxiliary Relay 3
---
F30
UNSIGNED INTEGER
PHASES REQ’D FOR OPERATION
FFFF
0 = Any One
---
1 = Any Two
---
2 = All Three
---
F31
UNSIGNED INTEGER - YES/NO
FFFF
0 = No
---
1 = Yes
---
F32
UNSIGNED INTEGER - DATA LOG MODE
FFFF
0 = Run to Fill
---
1 = Circulate
---
F33
UNSIGNED INTEGER
DATA LOG SIZE DETERMINATION
FFFF
0 = Automatic
---
1 = From Setpoint
---
F34
UNSIGNED INTEGER - DATA LOG SELECTION
FFFF
0 = None
---
1 = Log 1
---
2 = Log 2
---
3 = Log 1 and Log 2
---
F35
UNSIGNED INTEGER - DATA LOG STATUS
FFFF
0 = Stopped
---
1 = Running
---
Table 7–11: Memory Map Data Formats (Sheet 7 of 20)
CODE
DESCRIPTION
BITMASK