A–14
PQM POWER QUALITY METER – INSTRUCTION MANUAL
PULSE OUTPUT APPLICATION
APPENDIX A: APPLICATION NOTES
match the registration of the end receiver. For example, if the end receiver counts each
closure as 100 kWh and each opening as 100 kWh, the PQM Pulse Output Interval should
be set to 200 kWh.
The PQM Output Relays can be configured as Failsafe or Non-Failsafe to match the
normally open/closed configuration of the KY and KZ connections at the end receiver. The
K connection is always made to the COM connection of the designated PQM output relay,
and the Y and Z connections can be made to the N/O or N/C connections based upon the
type of end receiver.