4–32
PQM POWER QUALITY METER – INSTRUCTION MANUAL
S2 SYSTEM SETUP
CHAPTER 4: PROGRAMMING
2.Select the switch input message display under the subgroup
S2: SYSTEM SETUP \
SWITCH INPUT A
.
3.Use the
and
keys to change the blinking character
over the cursor. A space is selected like a character.
4.Press the
key to store the character and advance the cursor to the next
position. To skip over a character press the
key.
5.Continue entering characters and spaces until the desired message is displayed. If a
character is entered incorrectly, press the
key repeatedly until the
cursor returns to the position of the error, and re-enter the character.
•
SWITCH A/B/C/D FUNCTION:
Select the required function for each switch input. See
chapter 2 “Switch Inputs” for a description of each function. The NEW DEMAND
PERIOD, SETPOINT ACCESS, SELECT ANALOG OUTPUT and SELECT ANALOG INPUT,
PULSE INPUT 1, PULSE INPUT 2, PULSE INPUT 3, PULSE INPUT 4, CLEAR ENERGY and
CLEAR DEMAND functions can be assigned to only one switch input at a time. If an
attempt is made to assign one of these functions to more than one input, the flash
message
THIS SWITCH FUNCTION ALREADY ASSIGNED
will be displayed. If an
attempt is made via the serial port, no flash message will appear but an error code will
be returned.
•
SWITCH A/B/C/D ACTIVATION:
This setpoint determines the operating sequence of
the switch. Select OPEN if a switch activation is required for a switch input transition of
closed to open. Select CLOSED if a switch activation is required for a switch input
transition of open to closed.
•
SWITCH A/B/C/D TIME DELAY:
If the switch input function is assigned to ALARM,
AUX1, AUX2, or AUX3, this message will be displayed. Enter the required time delay in
this message.
VALUE
VALUE
STORE
STORE
STORE
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...