7–54
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
CURRENT
/VOLTAGE
CONFIG.
1050
Phase CT Primary
0 to
12000
****
5
A
F1
0 = OFF
1051
Neutral Current Sensing
0 to 2
1
---
F16
0 = OFF
1052
Neutral CT Primary
5 to 6000
5
A
F1
100 A
1053
VT Wiring
0 to 6
1
---
F15
0 = OFF
1054
VT Ratio
10 to
35000
1
0.1 xratio
F1
1.0:1
1055
VT Nominal Secondary Voltage
40 to 600
1
V
F1
120 V
1056
Nominal Direct Input Voltage
40 to 600
1
V
F1
600 V
1057
Nominal Frequency
50 to 60
10
Hz
F1
60 Hz
1058
CT Wiring
0 to 3
1
---
F44
0=A,B AND C
1059
Reserved
to
↓
↓
↓
↓
↓
↓
105F
Reserved
Table 7–10: PQM Memory Map (Sheet 38 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only