CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–37
POWER
QUALITY
0470
Ia Crest Factor
---
---
0.001 xCF
F1
N/A
0471
Ib Crest Factor
---
---
0.001 xCF
F1
N/A
0472
Ic Crest Factor
---
---
0.001 xCF
F1
N/A
0473
Ia Transformer Harmonic Derating Factor
---
---
0.01xTHDF
F1
N/A
0474
Ib Transformer Harmonic Derating Factor
---
---
0.01xTHDF
F1
N/A
0475
Ic Transformer Harmonic Derating Factor
---
---
0.01xTHDF
F1
N/A
0476
Reserved
0477
Reserved
HARMONIC
DISTORTION
0478
Phase A Current THD
---
---
0.1 x %
F1
N/A
0479
Phase B Current THD
---
---
0.1 x %
F1
N/A
047A
Phase C Current THD
---
---
0.1 x %
F1
N/A
047B
Neutral Current THD
---
---
0.1 x %
F1
N/A
047C
Voltage Van THD
---
---
0.1 x %
F1
N/A
047D
Voltage Vbn THD
---
---
0.1 x %
F1
N/A
047E
Voltage Vcn THD
---
---
0.1 x %
F1
N/A
047F
Voltage Vab THD
---
---
0.1 x %
F1
N/A
0480
Voltage Vbc THD
---
---
0.1 x %
F1
N/A
0481
Reserved
---
---
0.1 x %
F1
N/A
0482
Phase A Current THD - Maximum
---
---
0.1 x %
F1
N/A
0483
Phase B Current THD - Maximum
---
---
0.1 x %
F1
N/A
0484
Phase C Current THD - Maximum
---
---
0.1 x %
F1
N/A
0485
Neutral Current THD - Maximum
---
---
0.1 x %
F1
N/A
0486
Voltage Van THD - Maximum
---
---
0.1 x %
F1
N/A
0487
Voltage Vbn THD - Maximum
---
---
0.1 x %
F1
N/A
0488
Voltage Vcn THD - Maximum
---
---
0.1 x %
F1
N/A
0489
Voltage Vab THD - Maximum
---
---
0.1 x %
F1
N/A
048A
Voltage Vbc THD - Maximum
---
---
0.1 x %
F1
N/A
048B
Reserved
---
---
---
---
---
048C
Time - Hour/Min of Phase A Cur. THD Max
---
---
---
F22
N/A
048D
Time - Seconds of Phase A Cur. THD Max
---
---
---
F23
N/A
048E
Date - Mnth/Day of Phase A Cur. THD Max
---
---
---
F24
N/A
048F
Date - Year of Phase A Cur. THD Max
---
---
---
F25
N/A
0490
Time - Hour/Min of Phase B Cur. THD Max
---
---
---
F22
N/A
0491
Time - Seconds of Phase B Cur. THD Max
---
---
---
F23
N/A
0492
Date - Mnth/Day of Phase B Cur. THD Max
---
---
---
F24
N/A
0493
Date - Year of Phase B Cur. THD Max
---
---
---
F25
N/A
0494
Time - Hour/Min of Phase C Cur. THD Max
---
---
---
F22
N/A
0495
Time - Seconds of Phase C Cur. THD Max
---
---
---
F23
N/A
0496
Date - Mnth/Day of Phase C Cur. THD Max
---
---
---
F24
N/A
0497
Date - Year of Phase C Cur. THD Max
---
---
---
F25
N/A
0498
Time - Hour/Min of Neutral Cur. THD Max
---
---
---
F22
N/A
Table 7–10: PQM Memory Map (Sheet 21 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only