0473
Ia Transformer
Harmonic Derating
Factor
0.01 x
THDF
1
F1
-
52
0474
Ib Transformer
Harmonic Derating
Factor
0.01 x
THDF
1
F1
-
53
0475
Ic Transformer
Harmonic Derating
Factor
0.01 x
THDF
1
F1
-
54
0478
Phase A Current THD
0.1 x %
5.0%
F1
3
55
0479
Phase B Current THD
0.1 x %
5.0%
F1
3
56
047A
Phase C Current THD
0.1 x %
5.0%
F1
3
57
047B
Neutral Current THD
0.1 x %
5.0%
F1
3
58
047C
Voltage Van THD
0.1 x %
5.0%
F1
3
59
047D
Voltage Vbn THD
0.1 x %
5.0%
F1
3
60
047E
Voltage Vcn THD
0.1 x %
5.0%
F1
3
61
047F
Voltage Vab THD
0.1 x %
5.0%
F1
3
62
0480
Voltage Vbc THD
0.1 x %
5.0%
F1
3
63
0481
Reserved
------
------
---
---
64
04B4
Average Current THD
0.1 x %
5.0%
F1
3
65
04B5
Average Voltage THD
0.1 x %
5.0%
F1
3
66
0246
Phase A Current -
Minimum
1000ths of
nominal A
1 unit
F1
3
67
0247
Phase B Current -
Minimum
1000ths of
nominal A
1 unit
F1
3
68
0248
Phase C Current -
Minimum
1000ths of
nominal A
1 unit
F1
3
69
0249
Neutral Current -
Minimum
1000ths of
nominal A
1 unit
F1
3
70
024A
Current Unbalance -
Minimum
tenths of 1
percent
1 unit
F1
3
71
024B
Phase A Current -
Maximum
1000ths of
nominal A
1 unit
F1
3
Table 8–4: Point List for Analog Input/Output Change (Sheet 4 of 9)
POINT
MOBUS
REG
DESCRIPTION
UNIT /
VALUE
DEADBAND
FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...