CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–55
ANALOG
OUTPUT 1
1060
Analog Output 1 Main Type
0 to 59
1
---
F14
5=Avg Ph Current
1061
Analog Output 1 Main Min Value
See Analog Output Range Table on page –92
0
1062
Analog Output 1 Main Max Value
See Analog Output Range Table on page –92
0
1063
Analog Output 1 Alternate Type
0 to 59
1
---
F14
0=NOT USED
1064
Analog Output 1 Alternate Min Value
See Analog Output Range Table on page –92
0
1065
Analog Output 1 Alternate Max Value
See Analog Output Range Table on page –92
0
1066
Reserved
1067
Analog Output 1 Serial Value
1
---
F2
0
ANALOG
OUTPUT 2
1068
Analog Output 2 Main Type
0 to 59
1
---
F14
18=3Ph Real
Power
1069
Analog Output 2 Main Min Value
See Analog Output Range Table on page –92
0
106A
Analog Output 2 Main Max Value
See Analog Output Range Table on page –92
0
106B
Analog Output 2 Alternate Type
0 to 59
1
---
F14
0=NOT USED
106C
Analog Output 2 Alternate Min Value
See Analog Output Range Table on page –92
0
106D
Analog Output 2 Alternate Max Value
See Analog Output Range Table on page –92
0
106E
Reserved
106F
Analog Output 2 Serial Value
1
---
F2
0
ANALOG
OUTPUT 3
1070
Analog Output 3 Main Type
0 to 59
1
---
F14
19=3Ph Reactive
Pwr
1071
Analog Output 3 Main Min Value
See Analog Output Range Table on page –92
1072
Analog Output 3 Main Max Value
See Analog Output Range Table on page –92
1073
Analog Output 3 Alternate Type
0 to 59
1
---
F14
0=NOT USED
1074
Analog Output 3 Alternate Min Value
See Analog Output Range Table on page –92
1075
Analog Output 3 Alternate Max Value
See Analog Output Range Table on page –92
1076
Reserved
1077
Analog Output 3 Serial Value
1
---
F2
0
ANALOG
OUTPUT 4
1078
Analog Output 4 Main Type
0 to 59
1
---
F14
17=3Ph Power
Factor
1079
Analog Output 4 Main Min Value
See Analog Output Range Table on page –92
107A
Analog Output 4 Main Max Value
See Analog Output Range Table on page –92
107B
Analog Output 4 Alternate Type
0 to 59
1
---
F14
0=NOT USED
107C
Analog Output 4 Alternate Min Value
See Analog Output Range Table on page –92
107D
Analog Output 4 Alternate Max Value
See Analog Output Range Table on page –92
107E
Reserved
107F
Analog Output 4 Serial Value
1
---
F2
0
Table 7–10: PQM Memory Map (Sheet 39 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only