CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–73
F7
UNSIGNED INTEGER - COMMAND
FFFF
1 = Reset
---
2 = Alarm Relay On
---
3 = Alarm Relay Off
---
4 = Auxiliary Relay 1 On
---
5 = Auxiliary Relay 1 Off
---
6 = Auxiliary Relay 2 On
---
7 = Auxiliary Relay 2 Off
---
8 = Auxiliary Relay 3 On
---
9 = Auxiliary Relay 3 Off
---
10 = Set Clock Time
---
11 = Set Clock Date
---
12 = Display 40 character Flash Message for 5 s
---
13 = Simulate Keypress
---
14 = Clear Energy Values
---
15 = Clear Max. Demand Values
---
16 = Clear Min./Max. Current Values
---
17 = Clear Min./Max. Voltage Values
---
18 = Clear Min./Max. Power Values
---
19 = Clear Max. THD Values
---
20 = Clear Switch Input Pulse Count
---
21 = High Speed Sampling Trigger
---
22 = Upload Mode Entry 2
---
23 = Upload Mode Entry 1
---
F7
con’t
24 = Factory Setpoints Reload 2
---
25 = Factory Setpoints Reload 1
---
26 = Test Relays and LEDs
---
27 = Waveform Capture Trigger
---
28 = Start Data Log(s)
---
29 = Stop Data Log(s)
---
30 = Resize Data Logs
(valid only if both logs are stopped)
---
31 = Clear Event Record
---
32= Trigger Trace Memory
---
33= Re-arm Trace Memory
---
34= Clear All Demand
---
35= Clear Min./Max. Frequency
---
Table 7–11: Memory Map Data Formats (Sheet 2 of 20)
CODE
DESCRIPTION
BITMASK
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...