CHAPTER 4: PROGRAMMING
S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–25
FIGURE 4–14: Setpoints Page 2 – System Setup / Analog Outputs
•
ANALOG OUTPUT RANGE:
If the T20 option is installed, the Analog Outputs can be
configured to operate as 4 to 20 mA current sources or 0 to 20 mA current sources. All
four Analog Outputs will operate with the same range as selected in this setpoint.
•
ANALOG OUTPUT MAIN / ANALOG OUTPUT ALT:
If the PQM is used in conjunction
with programmable controllers, automated equipment, or a chart recorder, the
analog outputs can be used for continuous monitoring. Although parameters can be
selected for continuous analog output, all values are available digitally through the
communications interface. Applications include using a computer to automatically
shed loads as the frequency decreases by monitoring frequency or a chart recorder to
plot the loading of a system in a particular process.
Each of the analog outputs can be assigned to two of the parameters listed in Table
4–3:
. The analog output main selection is the default
selection and a programmable switch input can be programmed to multiplex the
ANALOG OUTPUT ALT
selection to the same output depending upon the open or
closed state of the switch input. See Section 4.3.4: Switch Inputs on page –31 for
] ANALOG OUTPUT 3
]
ANALOG OUTPUT 3 MAIN
NOT USED
MAIN 4 mA VALUE:
0
MAIN 20 mA VALUE:
0
ANALOG OUTPUT 3 ALT:
NOT USED
ALT 4 mA VALUE:
0
ALT 20 mA VALUE:
0
] ANALOG OUTPUT 4
]
ANALOG OUTPUT 4 MAIN
NOT USED
MAIN 4 mA VALUE:
0
MAIN 20 mA VALUE:
0
ANALOG OUTPUT 4 ALT:
NOT USED
ALT 4 mA VALUE:
0
ALT 20 mA VALUE:
0
SEE PREVIOUS PAGE
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
see ANALOG OUTPUT
PARAMETERS table
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...