4–30
PQM POWER QUALITY METER – INSTRUCTION MANUAL
S2 SYSTEM SETUP
CHAPTER 4: PROGRAMMING
3.Use the
and
keys to change the blinking character over
the cursor. A space is selected like a character.
4.Press the
key to store the character and advance the cursor to the next
position. To skip over a character press the
key.
5.Continue entering characters and spaces until the desired message is displayed. If a
character is entered incorrectly, press the
key repeatedly until the cur-
sor returns to the position of the error, and re-enter the character.
•
ANALOG IN MAIN/ALT UNITS:
This message allows the user to input a user defined 10
character alphanumeric name for the MAIN and ALT units. To enter the units, perform
the same steps as shown for analog input name.
•
MAIN/ALT 4 mA VALUE:
This message appears for each analog input and allows the
user to assign a numeric value which corresponds to the 4 mA end of the 4 to 20 mA
signal range.
•
MAIN/ALT 20 mA VALUE:
This message appears for each analog input and allows the
user to assign a numeric value which corresponds to the 20 mA end of the 4 to 20 mA
signal range.
•
ANALOG IN MAIN/ALT RELAY:
Analog input MAIN and ALT detection can either be
disabled, used as an alarm or as a process control. Set this setpoint to
OFF
if the
feature is not required. Selecting ALARM causes the alarm relay to activate and
displays an alarm message whenever a MAIN or ALT analog input condition exists.
Selecting an
AUXILIARY
relay causes the selected auxiliary relay to activate with no
message displayed. This is intended for process control.
•
ANALOG IN MAIN/ALT LEVEL:
When the measured MAIN or ALT analog input equals or
exceeds the level set by this setpoint, a MAIN or ALT analog input condition will occur.
•
ANALOG IN MAIN/ALT DELAY:
If the MAIN or ALT analog input equals or exceeds the
ANALOG IN MAIN/ALT LEVEL
setpoint value and remains this way for the time delay
programmed in this setpoint, an analog input condition will occur. If the
ANALOG IN
MAIN/ALT RELAY:
setpoint is set to ALARM, the alarm relay will activate and the
ANALOG IN MAIN/ALT ALARM
message will be displayed. If the setpoint
ANALOG IN
MAIN/ALT RELAY:
is set to AUX1, AUX2 or AUX3 the respective auxiliary relay will
activate and no message will be displayed after the delay expires.
VALUE
VALUE
STORE
STORE
STORE
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...
Страница 348: ...I 10 PQM POWER QUALITY METER INSTRUCTION MANUAL INDEX Courtesy of NationalSwitchgear com ...