background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Three-phase, four-module electricity meter

 

Description of the SIMLIC LS-3 meter 
series

 

The SIMLIC LS-3 series are three-phase, four-module electricity meters with an LCD display. 
They can be used for measurements in commercial and industrial applications. Depending on 
your needs, you can choose from three product models. 

LS-3F

 

- measurement and indication of active energy (kWh) and power (W), the meter 

indicates total energy consumption and consumption over time (RESET function) 

LS-3FD

  - measurement and indication of active energy (kWh) 

LS-3FB

  -measurement  and  indication  of  active  energy  (kWh)  consumed  and  exported 

(import/export) and power (W). It can be used to measure renewable energy. RESET function 
(measurement in a selected time) 

The RESET button located on the front of the LS-3F and LS-3FB meter performs two functions: 
- short pressing switches the particular views on the display, 
- pressing and holding for approx. 3 seconds resets the partial energy measurement. The meters 
are equipped with an additional pulse output, which makes it possible to connect the meter. 

Technical data

 

Safety instructions

 

Information for your safety 

SIMLIC  LS-3  series  electricity  meters  are  used  to  measure  the  electricity  consumption  in 
three-phase  networks  to  which  they  should  be  connected  by  a  qualified  electrician  in 
accordance  with  the  applicable  standards,  after  reading  this  manual.  Before  starting  the 
installation,  check  whether  the  connection  cables  are  live.  Make  sure  that  the  meter  is  not 
damaged,  deformed  or  any  elements  are  missing.  Consult  the  manufacturer  in  case  of 
malfunction. 

Correct use of the SIMLIC LS-3 series meter 

The basic factors necessary to ensure the proper operation of the device is proper transport, 
storage, installation and its connection. Do not forget about proper operation and ensuring the 
proper  condition  of  the  device  during  its  operation.  During  operation  of  the  device,  its 
components  may  be  under  voltage  dangerous  to  human  health.  You  must  be  particularly 
careful. 

use only insulated tools to operate the device, 
installation works should be carried out with the voltage off, 
the place for installation should be dry, 
the product should not be installed in potentially explosive areas or where it will be 
exposed to dust, mould or insects, 
 
make sure that the connecting cables are able to carry the maximum currents for a 
given meter, 
before starting the meter, make sure that the power cables are correctly connected 
to the meter terminals, 
touching the meter's connection terminals with bare hands, metal objects, 
uninsulated wire or other conductive objects creates a risk of electric shock, 
after installation, it is absolutely necessary to put on the terminal covers (protective 
covers), 
installation, inspections, optional repairs should be carried out by persons with 
appropriate qualifications, 
unauthorised persons, without proper qualifications, should never remove the 
protective covers or interfere with the meter components, 
the meter should be protected against falls and mechanical shocks, precise 
elements inside the device may be damaged, which will result in lack of accuracy of 
the measurements. 

The crossed-out bin symbol on your device indicates that the product marked with it must not be 
disposed of with household waste. After use, return the product to a collection point for electrical 
and electronic equipment or return it to your dealer. It is the responsibility of the user to return 
the  device  to  the  appropriate  collection  point  or  to  the  dealer  when  it  is  no  longer  used. 
Appropriate  segregation  of  waste  for  post-treatment,  recovery  or  destruction  contributes  to 
avoid negative environmental and health impacts and enables the recovery of the raw materials 
from which the product is made. For more detailed information on available collection points, 
please contact your local cleaning service or the shop where you have purchased the product. 

External dimensions

 

Specifications

 

Nominal voltage (Un) 

230V/400V AC (3~) 

Voltage measuring range 

80%~120% Un 

Insulating capacity 

 

- AC surge voltage 

4kV for 1 minute 

- surge, impulse voltage 

6kV-

1.2/50µS 

Base current (Ib) 

10A 

Maximum current (lmax) 

100A 

Reference current (Iref) 

20A 

Start-up meter current (Ist) 

0,04A 

Minimum current (Imin) 

0,5A 

Running current range 

0.4% lb~lmax 

Current overload 

30lmax for 0.01s 

Rated frequency 

50Hz ± 10% 

Own collection 

≤ 2W/10N/A 

Pulse output 

1000imp/kWh 

Maximum indication 

999999,9 kWh 

Performance criteria

 

Relative humidity (without condensation) 

≤ 90% 

Storage humidity 

≤ 95% 

Working temperature 

-

25°C - +55°C 

Storage temperature 

-

40°C - +70°C 

Active energy measuring accuracy 

Class B EN50470-1/3 

 

Class 1IEC 62053-21 

Protection level 

IP51 

Insulation class in the enclosure 

II 

Start-up  time 

10 seconds 

Mechanical environment 

Ml 

Electromagnetic environment 

E2 

Pollution degree 

 

Height 

100m

Width 

72mm 

Depth 

66mm 

 

Reviews: