background image

 

 

 

Qubino

       

 

 
 
The

 INNOVATIVE 

and 

SMALLEST

                         

                                                

 

 

 

Smart Meter 

 

 

ORDERING CODE 

Z-WAVE FREQUENCY 

ZMNHTD1 

868,4 MHz 

ZMNHTD2 

921,4 MHz 

ZMNHTD3 

908,4 MHz 

ZMNHTD4 

869,0 MHz 

ZMNHTD5 

916,0 MHz 

ZMNHTD8 

865,2 MHz 

This Z-Wave module is used for energy measurements in 

single-phase electrical power network and can be used in 

residential,  industrial  and  utility  applications.  Meters 

measure  energy  directly  in  2-wire  networks  according  to 

the  principle  of  fast  sampling  of  voltage  and  current 

signals.  A  built-in  microprocessor  calculates  energy, 

power and power factor from the measured signals.  

The  module  can  be  controlled  through  Z-wave  network 

and  it  acts  as  repeater  in  order  to  improve  range  and 

stability of Z-wave network.

 

It is designed to be mounted on DIN rail.

 

                       

 

Installation  

 

To prevent electrical shock and/or equipment 

damage

, disconnect electrical power: remove main 

fuse or put on OFF position a main disconnection 

switch (or circuit breaker if it is compliant to standard 

IEC947-2), before installation or any servicing.

  

 

Make sure, that no voltage is present in the 

installation.  

 

Prevent the disconnecting device from being 

switched on accidentally. 

 

Connect the module according to electrical diagram.  

 

Locate  the  antenna  far  from  metal  elements  (as  far 

as possible).  

 

Do not shorten the antenna. 

Danger of electrocution!  

 

Module  installation  requires  a  great  degree  of  skill 

and  may  be  performed  only  by  a  qualified  and 

licensed electrician. 

 

Even  when  the  module is  turned  off,  voltage  may  be 

present on its terminals. 

 

Note! 

Do  not  connect  the  module  to  loads  exceeding 

recommended  values.  Connect  the  module  only  in 

accordance to the below diagrams. Improper connections 

may be dangerous. 

Electrical  installation  must  be  protected  by  over  current 

protection  fuse 

with  rated  current  up  to  63A

,

  it  must  be 

used  according  to  wiring  diagram  to  achieve  appropriate 

overload protection of the module. 

Package contents 

 

Smart Meter

 

 
Electrical diagram 230VAC 
 
 

 

 

 

 

 

 

 

 

 

 

 

       

 

                              IR

 

                                                                  

 

              

 

           

 

 

 

  

                                        

 

 

 

 

 

 

 

 

 

 

Notes for the diagram: 

LI 

Live input

 

NI 

Neutral input

 

Lo 

Live output

 

No 

Neutral output

 

Input for IR external relay/Ext. relay 

2

 

Neutral lead for input 

Live lead for External relay output

 

Output for External relay (max. 3W)

 

Service  button  (used  to  add  or  remove 

module from the Z-Wave network). 

LED1 

Green - Power on (solid) / no ID (blinking 

slow  1s)  /  Inc./Exc.  mode  (blinking  fast 

0,5s)    

LED2 

Yellow on 

– output on (any) / Yellow off – 

outputs off (both) 

IR 

Output for IR external relay 

1imp/Wh 

Red - Pulse rate (On 

– no load indication) 

Measurements 

Voltage

 

Current

 

Power 

– Active

 

Power 

– Active total Import

 

kWh 

Power 

– Active total Export 

kWh 

Power 

– Reactive

 

var 

Power 

– Reactive total

 

kvarh 

Power 

– Apparent total

 

kVAh 

Power Factor

 

PF 

 
External relays  

It is possible to connect two external relay to Smart Meter 

module. One controlled by built-in optical (IR) 

communication port on the side, second controlled by 

output on terminal 5. 

 

 

 
 
 
 
 
 
 
 
 
Module  Inclusion  (Adding  to  Z-wave 
network)

 

 

Connect module to power supply  

 

enable add/remove mode on main controller 

 

auto-inclusion  (works  for  about  5  seconds  after 

connected to power supply) or 

 

press service button 

S

 for more than 2 second  

NOTE:  For  auto-inclusion  procedure,  first  set  main 

controller into inclusion mode and then connect module to 

power supply. 

Module 

Exclusion/Reset 

(Removing 

from Z-Wave network) 

 

Connect module to power supply  

 

bring module within maximum 1 Meter (3 feet) of the 

main controller, 

 

enable add/remove mode on main controller 

 

press service button 

S

 for more than 6 seconds. 

By this function all  parameters   of the module are set to 

default values and own ID is deleted. 

If service button S is pressed more than 2 and less than 6 

seconds module is

 

excluded, but configuration 

parameters   are not set to default values.

 

Association 

Association  enables  Smart  Meter  module  to  transfer 

commands  inside  Z-Wave  network  directly  to  other  Z-

Wave modules. 

Associated Groups: 

Group 1: Lifeline group (reserved for communication  with 

the main controller), 1 node allowed.

 

Configuration parameters   

Parameter no. 7 

– Input 1 switch function selection 

Available congig. parameters (data type is 1 Byte DEC): 

 

default value 4 

 

0 - disabled 

 

2 - IR external relay control 

– mono stable push 

button 

 

3 - IR external relay control - bi stable switch 

 

4 - External relay control 

– mono stable push button 

 

5 - External relay control 

– bi stable switch 

Parameter no. 10 - Activate / deactivate functions ALL 

ON / ALL OFF 

 

Available config. parameters (data type is 2 Byte DEC): 

 

default value 255 

 

255 - ALL ON active, ALL OFF active. 

 

0 - ALL ON is not active, ALL OFF is not active 

 

1 - ALL ON is not active, ALL OFF active 

 

2 - ALL ON active, ALL OFF is not active 

Smart  Meter  module  responds  to  commands  ALL  ON/ 

ALL  OFF  that  may  be  sent  by  the  main  controller  or  by 

other controller belonging to the system 

Parameter  no.  11  -  Automatic  turning  off  IR  external 

relay output after set time  

When  IR  external  relay  is  ON  it  goes  automatically  OFF 

after  time  defined  by  this  Parameter.  Timer  is  reset  to 

zero  each  time  the  module  receive  ON  command 

regardless from  where it comes (push button, associated 

module,  controller,..).  Available  configuration  parameters   

(data type is 2 Byte DEC): 

 

default value 0 

 

0 - Auto OFF disabled  

 

1  -  32535  =  1second  -  32535  seconds.  Auto  OFF 

enabled with define time, step is 1s. 

Parameter  no.  12  -  Automatic  turning  on  IR  external 

relay output after set time  

When  IR  external  relay  is  OFF  it  goes  automatically  ON 

after  time  defined  by  this  Parameter.  Timer  is  reset  to 

zero  each  time  the  module  receive  OFF  command 

regardless from  where it comes (push button, associated 

module,  controller,..).  Available  configuration  parameters   

(data type is 2 Byte DEC): 

 

default value 0 

 

0 - Auto ON disabled  

 

1  -  32535  =  1second  -  32535  seconds.  Auto  ON 

enabled with define time, step is 1s. 

Parameter  no.  13  -  Automatic  turning  off  External 

relay output after set time  

When External relay is ON it goes automatically OFF after 

time  defined  by  this  parameter.  Timer  is  reset  to  zero 

each  time  the  module  receive  ON  command  regardless 

from  where  it  comes  (push  button,  associated  module, 

controller,..).  Available  configuration  parameters  (data 

type is 2 Byte DEC): 

 

default value 0 

 

0 - Auto OFF disabled  

 

1  -  32535  =  1second  -  32535  seconds.  Auto  OFF 

enabled with define time, step is 1s. 

Parameter  no.  14  -  Automatic  turning  on  External 

relay after output set time  

When External relay is OFF it goes automatically ON after 

time  defined  by  this  parameter.  Timer  is  reset  to  zero 

each  time  the  module  receive  OFF  command  regardless 

from  where  it  comes  (push  button,  associated  module, 

controller,..).    Available  configuration  parameters  (data 

type is 2 Byte DEC): 

 

default value 0 

 

0 - Auto ON disabled  

 

1  -  32535  =  1second  -  32535  seconds.  Auto  ON 

enabled with define time, step is 1s. 

Parameter no. 40 

– Power reporting in Watts on power 

change  

Set  value  means  percentage,  set  value  from  0 

–  100  = 

0% - 100%. Available configuration parameters (data type 

is 1 Byte DEC): 

 

default value 10  

 

0 - reporting disabled  

 

1  -  100  =  1%  -  100%  Reporting  enabled.  Power 

report  is  send  (push)  only  when  actual  power  in 

Watts  in  real  time  changes  for  more  than  set 

percentage  comparing  to  previous  actual  power  in 

Watts, step is 1%. 

NOTE: if power changed is less than 1W, the report is not 

send  (pushed),  independent  of  percentage  set.

 

When 

reporting  Watts,  module  will  automatically  reports  also  V 

(Voltage),  A  (Amperes),  Power  factor,  kVar  (Reactive 

Power).   

Parameter  no.  42 

– Power  reporting in Watts by time 

interval 

Set  value  means  time  interval  (0 

–  32535)  in  seconds, 

when  power  report  is  send.  Available  config.  parameters   

(data type is 2 Byte DEC): 

 

default value 0  

 

0 - Reporting Disabled 

 

1  -  32535  =  1  second  -  32535  seconds.  Reporting 

enabled,  Power  report is  send  with time  interval  set 

by entered value. When reporting Watts, module will 

automatically reports also V (Voltage), A (Amperes), 

Power factor, kVar (Reactive Power).  

Parameter no. 45 

– Reset Power counters 

Available config. parameters (data type is 1 Byte DEC): 

 

default value 0 

 

0 - no function 

 

1 - reset counter 1 

– KWh  

 

2 - reset counter 2 

– kVARh 

 

4 - reset counter 3 

– kVAh 

Reviews: