![background image](http://html.mh-extra.com/html/ge/gek-106273l/gek-106273l_instruction-manual_134819090.webp)
PRODUCT DESCRIPTION
GEK-106273L
MIF Digital Feeder Protection
5-33
5.3.3.
PHASE / GROUND IOC SETTINGS (50PH / 50PL / 50NH / 50NL) (TABLE 2)
ENERVISTA MII
SETUP
HMI
DEFAULT
RANGE
STEP
Ph IOC High Set Table
2
50PH Function (Table
2)
F50PH T2
50PH Permission to Trip
50PH Trip Permission
T2
TRIP 50PH
T2
No Y/N NA
50PH Tap / Pickup
50PH Pickup T2
TAP 50PH T2 1 In (Phase)
0.1 – 30 In (Ph)
0.1 In (Ph)
50PH Time Delay
50PH Time Delay T2
TIME 50PH
T2
0 s.
0 – 600.00 s.
0.01 s.
Ph IOC Low Set Table 2
50PL Function (Table
2)
F50PL T2
50PL Permission to Trip
50PL Trip Permission
T2
TRIP 50PL T2
No
Y/N
NA
50PL Tap / Pickup
50PL Pickup T2
TAP 50PL T2
1 In (Phase)
0.1 – 30 In (Ph)
0.1 In (Ph)
50PL Time Delay
50PL Time Delay T2
TIME 50PL
T2
0 s.
0 – 600.00 s.
0.01 s.
Gnd IOC High Set Table
2
50NH Function (Table
2)
F50NH T2
50NH Permission to Trip
50NH Trip Permission
T2
TRIP 50NH
T2
No Y/N NA
50NH Tap / Pickup (1/5 A
ground)
50NH Pickup T2
TAP 50NH T2
1 In
(Ground)
0.1 – 30 In
(Gnd)
0.1 In (G)
50NH Tap / Pickup Value
(sensitive ground)
50NH Pickup T2
TAP 50NH T2
0.005 A
0.005-0.12 A
0.001 A
50NH Time Delay
50NH Time Delay T2
TIME 50NH
T2
0 s.
0 – 600.00 s.
0.01 s.
Gnd IOC Low Set Table
2
50NL Function (Table
2)
F50NL T2
50NL Permission to Trip
50NL Trip Permission
T2
TRIP 50NL
T2
No Y/N NA
50NL Tap / Pickup (1/5 A
ground)
50NL Pickup T2
TAP 50NL T2
1 In
(Ground)
0.1 – 30 In
(Gnd)
0.1 In (G)
50NL Tap / Pickup Value
(sensitive ground)
50NL Pickup T2
TAP 50NL T2
0.005 A
0.005-0.12 A
0.001 A
50NL Time Delay
50NL Time Delay T2
TIME 50NL
T2
0 s.
0 – 600.00 s.
0.01 s.
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...