PRODUCT DESCRIPTION
2-10
MIF Digital Feeder Protection
GEK-106273L
2.7
EVENTS (AVAILABLE IN OPTION 1 AND OPTION 2 MODELS)
The MIF stores a historical record with the last 32 events. Each event contains the event description, date and time (4
ms accuracy), the current values in phases and ground at that moment, and a summary of the status signals that can
produce events, and whether they were activated or not in that moment.
In the ENERVISTA MII SETUP there is a field called “EVENTS”, where the user can check how many events have
been produced since the last time that Events where deleted. If this number is higher than 32 (maximum number of
events stored), this means that from all the produced events, only the last 32 are stored.
This event record is stored in a
capacitor backed up RAM memory
.
The whole MIF functionality related to events is performed from the ENERVISTA MII SETUP software.
Inside the ADVANCED SETTINGS group, there is a sub-group called EVENT MASKS, from where the different
causes that can produce events can be masked. They are detailed in the SETTINGS section.
The following table shows a list of all possible events:
DESCRIPTION
OPTION 1
OPTION 2
50PH Pickup/Drop out
Yes
Yes
50PL Pickup/Drop out
Yes
Yes
50NH Pickup/Drop out
Yes
Yes
50NL Pickup/Drop out
Yes
Yes
51P Pickup/Drop out
Yes
Yes
51N Pickup/Drop out
Yes
Yes
49 Pickup/Drop out
Yes
Yes
50PH Trip
Yes
Yes
50PL Trip
Yes
Yes
50NH Trip
Yes
Yes
50NL Trip
Yes
Yes
51P Trip
Yes
Yes
51N Trip
Yes
Yes
49 Trip
Yes
Yes
General trip
Yes
Yes
50PH Trip enable/disable by digital input
Yes
Yes
50PL Trip enable/disable by digital input
Yes
Yes
50NH Trip enable/disable by digital input
Yes
Yes
50NL Trip enable/disable by digital input
Yes
Yes
51P Trip enable/disable by digital input
Yes
Yes
51N Trip enable/disable by digital input
Yes
Yes
49 Trip enable/disable by digital input
Yes
Yes
General trip enable/disable by digital input
Yes
Yes
Protection status in service/out of service
Yes
Yes
Digital output 1 active/non active
Yes
Yes
Digital output 2 active/non active
Yes
Yes
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...