![background image](http://html.mh-extra.com/html/ge/gek-106273l/gek-106273l_instruction-manual_134819202.webp)
ANNEX 6 STATUS LIST
GEK-106273L
MIF Digital Feeder Protection
16-3
NAME
DESCRIPTION
OPTION
0
OPTION
1
OPTION
2
settings group)
Events
Number of events produced since the last time they
were deleted
Active table
Shows which table is active (table 1 or table 2)
Frequency
Frequency value entered in the “Frequency” setting
(general settings group)
Alarm
Alarm contact status. This contact is enabled when
“Protection” is out of service, or when all trips are
disabled (either by setting or by digital input).
Output 1
Status of Auxiliary Output 1
Output 2
Status of Auxiliary Output 2
Output 3
Status of Auxiliary Output 3
Output 4
Status of Auxiliary Output 4
Input 1
Status of Digital Input 1
Input 2
Status of Digital Input 2
Ready
Status of the READY LED. Same as for the alarm
contact.
Trip LED
TRIP LED status
LED 1
LED 1 status
LED 2
LED 2 status
LED 3
LED 3 status
LED 4
LED 4 status
Logic 1
Output status of logic 1
Logic 2
Output status of logic 2
Logic 3
Output status of logic 3
Logic 4
Output status of logic 4
Table change
Shows whether the Table 2 selection by digital input
is active. If so, Table 2 is shown; if not, the set table is
activated.
Settings change
disabled
Shows whether the Settings Change is inhibited by
digital input. If so, it is not possible to change settings
or command operations from the PC or the MMI. The
table change is permitted by digital input.
Cold load pickup
Shows whether the cold load pickup is activated.
Breaker 52a
Status of the breaker terminal A.
Breaker 52b
Status of the breaker terminal B
Breaker status
Breaker status
Breaker failure
Indicates a breaker failure
Counter
Value of the I
2
counter
Number of openings
Number of openings
I2 Alarm
Active when I
2
counter value exceeds the counter
maximum limit, set in the BREAKER FAILURE TO
OPEN group of settings.
Local/remote
Active when the MMI is on the settings or operations
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...