![background image](http://html.mh-extra.com/html/ge/gek-106273l/gek-106273l_instruction-manual_134819054.webp)
PRODUCT DESCRIPTION
GEK-106273L
MIF Digital Feeder Protection
3-35
It is possible to change by hardware the contact configuration from normally open to normally closed (see the first
point of this document).
o
OUT1 normally closed and OUT2 normally open:
The hardware configuration corresponds to OUT1 NC and OUT2 NO. To operate with this hardware
configuration it is necessary to configure by software the OUT1 as NOT ASIGNED, so it never
change its state and remains closed, and OUT2 as required by the application (output configuration is
only available in models option 1 and 2).
o
OUT1 normally open and OUT2 normally closed:
The hardware configuration corresponds to OUT1 NO and OUT2 NC. To operate with this hardware
configuration it is necessary to configure by software the OUT2 as NOT ASIGNED, so it never
change its state and remains closed, and OUT1 as required by the application (output configuration is
only available in models option 1 and 2).
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...