LOGIC CONFIGURATION
GEK-106273L
MIF Digital Feeder Protection
7-5
49 Alarm
49 function pickup
Pickup
Pickup of any of the above mentioned functions
50Ha virtual trip
Virtual trip of Phase A 50PH unit
50Hb virtual trip
Virtual trip of Phase B 50PH unit
50Hc virtual trip
Virtual trip of Phase C 50PH unit
50La virtual trip
Virtual trip of Phase A 50PL unit
50Lb virtual trip
Virtual trip of Phase B 50PL unit
50Lc virtual trip
Virtual trip of Phase C 50PL unit
51 a virtual trip
Virtual trip of Phase A 51P unit
51 b virtual trip
Virtual trip of Phase B 51P unit
51 c virtual trip
Virtual trip of Phase C 51P unit
50PH virtual trip
Trip condition for 50PH function exists
50NH virtual trip
Trip condition for 50NH function exists
50PL virtual trip
Trip condition for 50PL function exists
50NL virtual trip
Trip condition for 50NL function exists
51P virtual trip
Trip condition for 51P function exists
51N virtual trip
Trip condition for 51N function exists
49 virtual trip
Trip condition for 49 function exists
General virtual trip
Any virtual trip of the above mentioned functions
50PH disabled
Function 50PH disabled
50NH disabled
Function 50NH disabled
51P disabled
Function 51P disabled
51N disabled
Function 51N disabled
50PL disabled
Function 50PL disabled
50NL disabled
Function 50NL disabled
49 disabled
Function 49 disabled
Trip disabled
Trip of all functions disabled
Output 1
Digital output 1
Output 2
Digital output 2
Output 3
Digital output 3
Output 4
Digital output 4
Input 1
Digital input 1
Input 2
Digital input 2
General Input
General input function
Settings change disabled
Active means that settings or tables can not be change.
It is only possible to switch to T2 by digital input Table change
Breaker 52 a
This function set means breaker close
Breaker 52 b
This function set means breaker open
Table change
Set means that active table is T2
Reset means that active table is in General Settings table
Breaker failure to open
Output of the breaker failure to open function, when this function is
enabled
Breaker status
When breaker failure is enabled and breaker is connected to
input1/2
I2 Alarm
Output of the I
2
counter function
Cold load pickup
Output of the Cold load pickup function, when this function is
enabled
E2PROM failure
Active when an E2prom management failure is detected
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...