PRODUCT DESCRIPTION
2-18
MIF Digital Feeder Protection
GEK-106273L
THERMAL IMAGE UNIT (49)
Current:
Pickup Level:
Dropout Level:
Level Accuracy:
Fundamental
0.10 to 2.40 In in steps of 0.01 x In
Between 97% and 98% of Pickup Level
±
1% at In
±
3% in the complete range
Heating Constant
τ
1:
Cooling Constant
τ
2:
Thermal Image Alarm:
Timing Accuracy:
From 3 to 600 min in steps of 1 min.
From 1 to 6 times
τ
1 in steps of 1.
From 70% to 100% I
pickup
in steps of 1%
5% for operate times greater than 2 sec.
2.13.2. METERING
FUNCTIONS
FUNDAMENTAL CURRENT
Accuracy:
±
1% at In
±
3% in the complete range
2.13.3. INPUTS
AC CURRENT
Secondary Rated Current:
Frequency:
Relay Burden:
Current Withstand:
1m 5 A depending on the selected model., or 50 mA for sensitive
ground models
50 / 60 Hz
±
3 Hz (The unit can be set to 50 or 60 Hz)
< 0.2 VA @ In = 5A secondary
< 0.08 VA @ In = 1A secondary
< 0.08 VA @ In = 1A sensitive ground, secondary
4 x In continuously.
100 x In for 1 sec.
DIGITAL INPUTS
Voltage Level:
Recognition Time:
300 Vdc maximum
< 4 ms
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...